background image

1.

TURN (DEPRESS) MANUAL GAS COCK KNOB ON COMBINATION VALVE TO OFF.

2.

TURN BURNER POWER ON. SET THERMOSTAT OR OPERATING CONTROL TO 

CALL FOR HEAT. 

LET MOTOR RUN 5 MINUTES

TO PURGE COMBUSTION 

CHAMBER AND CHIMNEY.

3.

SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM 
TEMPERATURE.

4.

TURN MANUAL GAS COCK KNOB ON COMBINATION VALVE TO 

PILOT

DEPRESS KNOB, OR RED BUTTON IF SO EQUIPPED, AND HOLD.

5.

PUSH PIEZO IGNITOR BUTTON SEVERAL TIMES TO LIGHT THE PILOT.

6.

AFTER ONE MINUTE, RELEASE MANUAL GAS COCK KNOB ON COMBINATION
VALVE, OR RED BUTTON IF SO EQUIPPED, AND TURN TO 

ON

.

7.

ADJUST THERMOSTAT OR OPERATING CONTROL TO DESIRED SETTING.

TO SHUT OFF

1.

TURN (DEPRESS) MANUAL GAS COCK KNOB ON COMBINATION VALVE TO 

OFF

.

2.

TURN BURNER POWER OFF.

SHOULD OVERHEATING OF THE GAS UTILIZATION EQUIPMENT OCCUR:

1.

SHUT OFF THE MAIN MANUAL SHUT-OFF VALVE TO THE EQUIPMENT.

2.

DO NOT SHUT OFF THE POWER SWITCH TO THE ECONOMITE BURNER, OR THE 

EQUIPMENT PUMP OR BLOWER.

Make sure the thermostat and operating controls are calling for heat. Defective wiring or loose
connections can simulate the component defects outlined below. Check associated wiring before
replacing a component. 

ELECTRICAL AND FLAME CHECKS MUST BE MADE IN ORDER LIST-

ED.

A.

Manual Gas Cock Knob on Combination Valve, or red button if so equipped, is not 
depressed in the 

PILOT

position.

B.

Main Manual Shut-Off Valve is not in open position.

C.

Air in pilot gas line (See Section 

VIII Initial Start-up/Adjustment

).

D.

High or low pilot flame gas pressure (See Section 

IX Venturi Casting and Pilot

).

E.

Clogged pilot orifice(s) (See Section 

IX Venturi Casting and Pilot

)

.

F.

Defective ignitor, ignitor wires, spark rod or improper spark gap (See Figure 8).

G.Excessively high or negative draft condition (See Section 

I Ventilation

and Section 

IV 

Chimney, Vent Connector and Draft Control

).

A.

Excessively high or negative draft condition (See Section 

I Ventilation

and Section 

IV 

Chimney, Vent Connector and Draft Control

).

B.

High or low pilot flame gas pressure ( See Section 

IX Venturi Casting and Pilot

).

C.

Burner tube extends into combustion chamber (See Section 

III Combustion Chamber

).

D.

Lint or dust in pilot (See Section 

IX Venturi Casting and Pilot

).

E.

Clogged pilot orifice(s) (See Section 

IX Venturi Casting and Pilot

).

F. 

Defective thermocouple (See Section 

IX Venturi Casting and Pilot

).

G.Defective pilotstat safety control (See Section 

IX Venturi Casting and Pilot

).

H.

Clogged pilot filter in Combination Valve; entire valve must be replaced.

A.

Confirm 120V between strip terminals 

1

and 

2

and verify the circuit polarity and electrical 

ground between strip terminal 1 and burner chassis metal.

B.

Check 24V* operating control circuit;

1. Between left strip terminal 

T

and 

GND

.

a. No voltage, transformer defective.
b. Very low voltage*, circuit overloaded or transformer defective.

2. Between right strip terminal 

T

and 

GND

.

No voltage, circuit between 

T

and 

T

is open.

C.

Confirm 120V between strip terminal 

2

and motor relay terminal 

4

1. No voltage, motor relay is defective.
2. Voltage present, motor is defective.

11

Lighting Instructions

Trouble Chart

I. Pilot Will Not Light

II. Pilot Goes Out

Frequently

III. Motor Will Not Run

Summary of Contents for Economite 400B-02 Series

Page 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Page 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Page 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Page 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Page 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Page 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Page 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Page 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Page 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Page 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Page 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Page 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Reviews: