WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - OWNER´S & INSTALLATION MANUAL

Current humidity or current temperature
display.

Keep the “set” button pressed for longer
than 5 secs.

Function s

.

=Humidity
=Dehumidity

Delayed time on the output. Used mainly
for device protection and in case of very
frequent switching on and switching off.

Setting of the deviation type.

Pn=+/- deviation

Setting of the humidity hysteresis (zone
of insensitiveness) - difference between
closure and opening points.
In case the control circuit reacts too
slowly,  reduce the hysteresis. In case the
control circuit is unstable (switches on and
off alternately), increase the hysteresis.

The correction function is used in case of
difference between the currently shown
value and the real exact value (detected
by etalon, e.g.)

HEt /heating/ Switching on of the heating
element on the humidity sensor FOX-2SH
is used for its prevention from misting, in
case the humidity is higher than 95% RH.

Switching on the “Lock function” - function
of set values´protection.

Lon= switching on the “Lock function”
LoF= cancellation of

Programming point “1”
Setting of the main output´values

etting

P=+deviation

the “Lock function”

Program setting

By keeping the “set” button pressed for longer than 5 secs, the setting gets finished and you return to a mode of current
humidity display.
In case of inactiveness for longer than 30 secs, this is done automatically.

Setting of the additional output
which is not connected.
Don´t perform any settings here
and return to the point

Summary of Contents for DRY 300 METAL

Page 1: ...WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S INSTALLATION MANUAL MODEL DRY 300 500 SILVER METAL ...

Page 2: ...purpose as described in the attached instructions for use Repairs and relocations must be performed only by a service technician Do not place any objects on the surface of the device 2 WALL MOUNTED SWIMMING POOL DEHUMIDIFIER OWNER S INSTALLATION MANUAL 1 SAFETY MEASURES 2 USAGE SPECIFICATION The units are designed especially for use in indoor swimming pools spas and saunas They can also be very us...

Page 3: ...ted value blinks By pressing the or button the requested value changes By repressing the set button after the requested value has been changed OK symbol appears and the requested value is saved isplay The current humidity or temperature is shown on display By pressing the button when the current humidity is being displayed the current temperature will be shown By pressing the button when the curre...

Page 4: ...rrection function is used in case of difference between the currently shown value and the real exact value detected by etalon e g HEt heating Switching on of the heating element on the humidity sensor FOX 2SH is used for its prevention from misting in case the humidity is higher than 95 RH Switching on the Lock function function of set values protection Lon switching on the Lock function LoF cance...

Page 5: ... done only using grooming articles suitable for rustless steel surfaces In case there is a water dripping from the equipment check whether a condensate pipe is not obstructed At least once a year it is necessary to have the unit checked and cleaned by a service specialist This is necessary in order to secure a long operational life of the device Cleaning the interior parts of the device by a user ...

Page 6: ...cover 6 2 Equipment fixation Model DRY 300 SILVER METAL Model DRY 500 SILVER METAL TOP EDGE OF THE DEVICE BRACKET SPIRIT LEVEL FIXATION SLOTS The cover can be dismounted after releasing two screws DRY 300 S or three screws DRY 500 S at the bottom of the device Release the screws pull the bottom part of the cover toward yourself and then by lifting it shortly rake down the cover from the rear plate...

Page 7: ...minimum 18 mm 6 5 Condensate drain DRY 300 SILVER METAL and DRY 500 SILVER METAL with connections front view Connecting the device onto the mains and protection securing must satisfy the requirements of relevant norms Connection requirements are the following 220 240 V 50Hz protection 10A DRY 300 SILVER METAL and 16A DRY 500 SILVER METAL with a mains fuse that has a current carrying differential d...

Page 8: ...hen it must be raised up to the height of 2500 mm from the swimming pool surface if the pool is embedded under the floor then the unit must be raised up to the height of 2500 mm from the floor It is inevitable to locate the device outside the zones where cleaning with splashing water is supposed or it must be protected by a current protector with a current carrying differential disconnecting capac...

Page 9: ...e LPHW into the element under pressure it is necessary to bleed the heater element The bleeding valve is located on the feeder pipe of the LPHW heater element To secure that the LPHW heater element works always at full heat output blowing onto the unit by a fan must be provided even when no dehumidification is being performed Therefore when using the LPHW heater element the switch of fan operation...

Page 10: ...tection Conductor A A mm 2 Pipe for condensate delivery min interior diameter Sizing width x height x depth Package sizing width x height x depth Weight net in package mm mm mm kg Dehumidifier efficiency rate DER Max pressures in the system HP LP bar Refrigerant R 410 A kg Mechanical Protection IP DEHUMIDIFICATION PERFORMANCE 7 Technical data 30 60 33 66 42 83 47 101 22 35 20 100 440 22 35 20 100 ...

Page 11: ...FROM BEHIND CONDENSATE DRAIN FROM THE BEHIND PIPE WITH AN INTERNAL DIAMETER OF MINIMUM 16 mm CONSOLE SLIPPING OUT FROM A CONSOLE PREVENTING POSITION SECURING FROM BEHIND SLIPPING OUT FROM A CONSOLE PREVENTING POSITION SECURING FROM BEHIND CONDENSATE DRAIN FROM THE BEHIND PIPE WITH AN INTERNAL DIAMETER OF MINIMUM 16 mm POWER SUPPLY FROM THE BEHIND CYSY WIRE 3C x 1 5 mm 2 POWER SUPPLY FROM THE BEHIN...

Page 12: ...NUAL WIRING DIAGRAM OF MODEL MICROWELL DRY 300 SILVER METAL DRY 300 Standard DRY 300 EASY 200 HYG 6001 DRY 300 LPHW Solenoid METAL DRY 300 1 DRY 300 1 DRY 300 2 SILVER DRY 300 1 DRY 300 1 DRY 300 2 DRY 300 1 Note Producer reserves right to make changes on wiring 12 ...

Page 13: ...13 WALL MOUNTED SWIMMING POOL DEHUMIDIFIER OWNER S INSTALLATION MANUAL Note Producer reserves right to make changes on wiring DRY 300 2 Note Producer reserves right to make changes on wiring ...

Page 14: ...NUAL WIRING DIAGRAM OF MODEL MICROWELL DRY 500 SILVER METAL DRY 500 Standard DRY 500 EASY 200 HYG 6001 DRY 500 LPHW Solenoid METAL DRY 500 1 DRY 500 1 DRY 500 2 SILVER DRY 500 1 DRY 500 1 DRY 500 2 DRY 500 1 Note Producer reserves right to make changes on wiring 14 ...

Page 15: ...15 WALL MOUNTED SWIMMING POOL DEHUMIDIFIER OWNER S INSTALLATION MANUAL Note Producer reserves right to make changes on wiring DRY 500 2 Note Producer reserves right to make changes on wiring ...

Page 16: ... Screw 3 5 x 13 9 24 Rubber grommet d15 DA 110 150 10 4 25 Rubber grommet d30 DA 230 300 20 4 26 Condensate pipe d18x3 1m 1 Position Component Number of pieces 1 Metal Stainless steel cover 1 1 1 Digital humidistat FOX 2SH 1 1 2 Humidity sensor DS SH104 1 2 Back metal sheet 1 3 Metal sheet in front of the exchanger 1 4 Metal sheet above the exchanger 1 5 Metal sheet under the compressor 1 6 Ventil...

Page 17: ...cil ppm 25 50 Ozone ppm 0 8 1 0 Maximum copper content ppm max 2 Aquamatic single purifier ppm max 2 Tarn clean purifier ppm max 2 Sherwood purifier ppm max 2 TRANSPORT INSTRUCTIONS The dehumidifiers must be transported only in the original packaging and in a vertical position Make sure that the dehumidifier cannot turn over or fall down during transportation Do never put the dehumidifier aside It...

Page 18: ......

Page 19: ...SNP 2018 42 927 01 Šaľa Slovakia Phone 421 31 7020 540 1 Fax 421 31 7020 542 E mail microwell microwell sk www microwell eu MICROWELL Ltd Distributed by Version 2013 07 16 ...

Reviews: