WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - OWNER´S & INSTALLATION MANUAL
Current humidity or current temperature
display.
Keep the “set” button pressed for longer
than 5 secs.
Function s
.
=Humidity
=Dehumidity
Delayed time on the output. Used mainly
for device protection and in case of very
frequent switching on and switching off.
Setting of the deviation type.
Pn=+/- deviation
Setting of the humidity hysteresis (zone
of insensitiveness) - difference between
closure and opening points.
In case the control circuit reacts too
slowly, reduce the hysteresis. In case the
control circuit is unstable (switches on and
off alternately), increase the hysteresis.
The correction function is used in case of
difference between the currently shown
value and the real exact value (detected
by etalon, e.g.)
HEt /heating/ Switching on of the heating
element on the humidity sensor FOX-2SH
is used for its prevention from misting, in
case the humidity is higher than 95% RH.
Switching on the “Lock function” - function
of set values´protection.
Lon= switching on the “Lock function”
LoF= cancellation of
Programming point “1”
Setting of the main output´values
etting
P=+deviation
the “Lock function”
Program setting
By keeping the “set” button pressed for longer than 5 secs, the setting gets finished and you return to a mode of current
humidity display.
In case of inactiveness for longer than 30 secs, this is done automatically.
Setting of the additional output
which is not connected.
Don´t perform any settings here
and return to the point