Chapter 7 Installation
3. Connect the antenna extension or antenna directly to the antenna connector of the
myDatalogEASY IoTmini (see "Overview" on page 20)
Important note:
Do not apply too much force when tightening the antenna. Do not use any
tools to tighten the antenna or antenna extension; only tighten it manually.
4. Switch the voltage supply of the myDatalogEASY IoTmini back on.
The following step is not mandatory.
5. Check whether the connection to the myDatanet server has worked correctly (see "Testing
communication with the device" on page 69).
7.5.3 Technical details about the universal inputs
Note:
The universal inputs 3 and 4 are only available if the RS485 interface is not used.
Note:
The universal inputs are not electrically isolated.
7.5.3.1 0/4 to 20mA mode
Note:
Above 23,96mA, the relevant input becomes highly resistive (safety shutdown to prevent damage to the
universal input).
Resolution
6,3µA
I
max
23,96mA
Load
96Ω
7.5.3.2 0 to 2V mode
Resolution
610µV
U
max
2,5V
Load
10k086
7.5.3.3 0 to 10V mode
Resolution
7,97mV
U
max
32V
Load
4k7
Rev. 01
55