5. MAIN MENU 

 

TX= XXX C

 

Pump Off

 

“TX”

 - indicate current selected temperature channel. To select

another   channel,   operator   must   use  

UP

  and  

DOWN

  button

( default value that is displayed after power-up is Tb) 

“XXX” 

- temperature value in degree.

Pumpe Aus” or “PumpeEin”

 - display state of pump 

The status of the heater is not indicated.

SR03

 has four buttons UP,DOWN,MODE and SET .

UP

 and 

DOWN

 are of general 

purpose. 

SET 

button is use for parameters adjustment. 

MODE

  is use for modes switch. The 

three modes are as follows :

- AUTO

 – automatic pump control 

- ON 

– absolutely pump switch on 

- OFF 

– absolutely pump switch off 

Pump control  rules by priority  in AUTO mode

Condition

Pump state 

Situation

Тb > “AlarmTb” 

 Pump Off  

 Boiler overheating  

Ts > “AlarmTs”

Pump Off

Installation overheating  danger

Ts < “AlarmFr” 

 Pump On

 Installation freezing danger 

Ts < “minTs”

Pump Off

 Low environmental temperature 

To > “AlarmTo”

Pump Off  

Solar panel temperature set has achieved

Ts – To  >  “DeltaSP”

Pump On

 Heating from Solar panel 

Figure 6

. Response of the controller according to the temperature of the solar panel

Document  edition 

2020-04-22

5

Summary of Contents for SR 03

Page 1: ...COMPETENCE IN MEASUREMENT SOLAR AND HEATING SYSTEMS TEMPERATURE CONTROLLER SR 03 TECHNICAL DESCRIPTION AND USER MANUAL PLOVDIV 2020 Document edition 2020 04 22...

Page 2: ...imensions WxHxL Wall Mounting Housing 125 85 58 mm DIN rail M36 70x86x57 Box Material Wall Mounting Housing MS C4 Plastic DIN rail M36 Noryl VO1550 black base Lexan 940 gray upper Weight max 450 g Lev...

Page 3: ...2 Front panel of device in wall mount housing 3 TERMINALS AND CONNECTIONS Figure 3 Connection of device in wall mount housing Document edition 2020 04 22 3 Pt 1000 Input Ts Tb To 220V Fuse K1 K2 Solar...

Page 4: ...depending of differences in temperature at measuring points The heater is controlled by temperature set point independently of the pump mode Tb To Ts Pump Heater Tb temperature sensor is placed on the...

Page 5: ...t MODE is use for modes switch The three modes are as follows AUTO automatic pump control ON absolutely pump switch on OFF absolutely pump switch off Pump control rules by priority in AUTO mode Condit...

Page 6: ...s applied After passing through all parameters the main menu is activated again This also happens if no action is taken during the setting for 15 seconds 6 SYSTEM PARAMETERS Parameters Factory setting...

Page 7: ...action area 3 T Jump 3 10 0 255 0 2 s Time of perception of measurement outside Jump 3 Alarm s 90 0 250 C Ts alarm pipeline overheating in automatic mode see pump control rules AlarmFr 4 50 50 C Insta...

Page 8: ...rt bad conservation wrong exploitation naturedisasters not following the instructions and the cases when there is an attempt to fix anydefects by other people In those cases the issue is being fixed o...

Reviews: