background image

13

Since 1965

MicroMetl

Economizing

Figure 29 – Enthalpy Curve Boundaries

9901-2022 SINGLE OUTSIDE AIR ENTHALPY 

SENSOR

When using the 9901-2022 (Honeywell C7400S) enthalpy sensor 

(See Figure 30) for outside air changeover, the existing 9901-2021  

(Honeywell C7250) dry bulb sensor must be removed if applicable. 

See Figure 1. When the enthalpy sensor’s OA temperature, 

enthalpy and dew point are below the respective setpoints, the 

outside air can be used for free-cooling. When any of these is 

above  the  setpoint,  free-cooling  will  not  be  available.  Figure  29 

shows the enthalpy boundaries in the W7220 Jade controller. 

There are (5) enthalpy boundaries (setpoints ES1 thru ES5), which 

are defined by dry bulb temperature, enthalpy, and dew point. ES3 

is the default setting. Table 7 shows the High Limit Curves for each 

setting. 

Important:  to  use  the  9901-2022  sensor  for  outside  air 

sensor, the dipswitches on the sensor must be set to OFF-OFF-

OFF. See Table 8.

The (2) gray wires with a plug from the economizer harness in the 

return chamber plug directly into the 9901-2022 enthalpy sensor. 

See Figures 23 and 28 for wiring.

Table 7 – Single Enthalpy and Dual Enthalpy High Limit Curves 

ENTHALPY 

CURVE

TEMP. DRY

BULB (F)

TEMP.

DEWPOINT (F)

ENTHALPY

(btu/lb/da)

POINT P1

POINT P2

TEMP. (F)

HUMIDITY 

(%RH)

TEMP. (F)

HUMIDITY 

(%RH)

ES1

80

60

28.0

80

36.8

66.3

80.1

ES2

75

57

26.0

75

39.6

63.3

80.0

ES3

70

54

34.0

70

42.3

59.7

81.4

ES4

65

51

22.0

65

44.8

55.7

84.2

ES5

60

48

20.0

60

46.9

51.3

88.5

HL

86

66

32.4

86

38.9

72.4

80.3

Figure 30 - 9901-2022 (C7400S) Dimensional, 

connection and switching information

Table 8 – 9901-2022 Sensor Dip Switch Settings 

USE

DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3

1

2

3

DA

OFF

ON

OFF

RA

ON

OFF

OFF

OA

OFF

OFF

OFF

DA -

 Discharge Air (not used on economizer)

RA - 

Return Air

OA -

 Outside Air

Default Setting = OFF-OFF-OFF

D

A

R

A

O

A

1

2

3

S-Bu

s

Temp & Humidity

9901-2022

4-1/4

2-3/4

2-1/64

S-B

u

s

Summary of Contents for ECD-SRTCA-D2

Page 1: ...Foremost HVAC Accessory Manufacturer Economizer ECD SRTCA D2 Install Guide...

Page 2: ...Table of Contents Topic Page Number General 1 Topic Page Number General Install Instructions 1...

Page 3: ...ating the compressors when the outdoor air is too humid integrating the compressor with outdoor air when free cooling is available and locking out the compressor when outdoor air temperature is too co...

Page 4: ...581J 551J 04 06 549J 547J 559J 582J 04 06 548J 580J 558J 04 07 Dry Bulb OA Sensor ECD SRT12CA D2DH Enthalpy OA Sensor ECD SRT12CA D2EH Large Cabinet 581J 551J 07 12 580J 558J 08 14 548J 08 12 549J 07...

Page 5: ...California Energy Commission Title 24 prescriptive section 140 4 damper leakage etc and mandatory section 120 2 i for Fault Detection and Diagnostic controls Economizers meet ASHRAE 90 1 damper leaka...

Page 6: ...t wiring harness See Figure 5 Note the 12 pin jumper plug should be saved for future use in the event that the economizer is ever removed The jumper plug is not needed as long as the economizer is ins...

Page 7: ...ect 10 Pin Jade Plug to Central Terminal Board Figure 11 Connect Red and Brown Wires to Central Terminal Board Step 14 Connect the White wire from the Jade controller harness to the W1 terminal on the...

Page 8: ...he divider between the control box and the indoor blower section See Figure 14 Important See note below Figure 14 Route 9962 0407 SAOEXT Harness to Indoor Blower Section See note below Some control bo...

Page 9: ...rness See note For 48 50LC 07 12 Instructions see pages 10 12 Figure 17 Economizer Hood Assembly ECONOMIZER P N A B C D SHIP WT ECD SRT12CA D2 H 30 37 17 43 19 05 29 5 55 lb ECD SRT34CA D2 H 40 37 22...

Page 10: ...unit control box panel See Figure 6 Economizer performance charts are below See base unit installation manual to make adjustments to meet building ventilation requirements Economizer Hood Filter Door...

Page 11: ...W7220 JADE Controller Field Mounted in Unit Control Box MAT MAT OAT OAT ACT 24V ACT COM S BUS S BUS EXH1 IAQ COM ACT 2 10 AUX1 OUT IAQ 2 10 E GRD AUX2 IN Y1 IN Y1 OUT Y2 OUT Y2 IN OCC C R 10 Pin Femal...

Page 12: ...0LC 07 12 units only Figure 24 Remove Complete Harness Factory Attached to W7220 Controller Figure 24A 9962 0407 SAOEXT Not Used on 48 50LC 07 12 Units Note The complete 4 wire 9962 0407 SAOEXT harnes...

Page 13: ...indoor blower Confirm that the screws do not interfere with blower rotation See Figure 15 IMPORTANT The brown and orange wires in the indoor blower section for the mixed air sensor have spade terminal...

Page 14: ...trol box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220 controller from the Carrier factory is removed and not...

Page 15: ...2 sensor for outside air sensor the dipswitches on the sensor must be set to OFF OFF OFF See Table 8 The 2 gray wires with a plug from the economizer harness in the return chamber plug directly into t...

Page 16: ...ness Provided in 9901 2022 DIFF JC2 Kit DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZER OFF WHEN DESCRIPTION FIXED DRY BULB 1 3 5 11 16 OAT exceeds 75 F 2 4 10 OAT exceeds 73 F 6 8 9 OAT exce...

Page 17: ...90 1 require that the economizer s faults be accessible by operating or service personal or annunciated locally on zone thermostat To setup remote monitoring on the controller under SYSTEM SETUP AUX1...

Page 18: ...nical units is the Honeywell W7220 which is to be located in the RTU base unit s Control Box See Fig 35 for button description of the W7220 controller The W7220 controller provide the following 2 line...

Page 19: ...UT MIN POS The minimum position allows for ventilation even when not in the free cooling mode If you have a single speed unit there will be only one minimum position setting The default is 2 8 volts b...

Page 20: ...sensor is connected and displays measured discharge temperature Displays if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMP...

Page 21: ...ected Setpoint for Demand Control Ventilation of space Above the setpoint the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint MIN POS 2 8 V 2 t...

Page 22: ...3000 ppm Increment by 50 CO2 ppm span to match CO2 sensor STG3 DLY 2 0h 0 min 5 min 15 min then 15 min intervals Up to 4 h or OFF COOLING STAGE 3 DELAY Delay after stage 2 for cool has been active Tu...

Page 23: ...0 terminal provides 24 Vac out ACT UNDER V n a n a ACTUATOR VOLTAGE LOW Voltage received at actuator is below expected range ACT OVER V n a n a ACTUATOR VOLTAGE HIGH Voltage received at actuator is ab...

Page 24: ...c Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source ACT 2 10 2 10 Vdc Damper Actuator Output 2 10 Vdc ACT COM COM Damper Act...

Page 25: ...command dry bulb outdoor enthalpy differential dry bulb or differential enthalpy a call for cooling Y1 closes at the thermostat will cause the economizer control to modulate the dampers open and close...

Page 26: ...to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always illuminated What is a good setpoint for the Mixed Air Tempera ture MA...

Reviews: