Step 5:

 Ensure economizer is square (tol/- 1/32"). Screw 

the  economizer  to  the  unit  along  both  side  flanges  and  bottom 

flange. See Figure 3.

Step 6:

 Remove the red tape securing the relief dampers for 

shipping purposes. Relocate the outside air sensor from its shipping 

location to its operating position, see Fig. 1

Step 7:

 If an economizer with a dry bulb sensor will be operating 

with an enthalpy outside air sensor, remove the factory installed 

9901-2021 dry bulb sensor from the front face of the economizer 

(see  Figure  1),  and  install  the  accessory  enthalpy  sensor  9901-

2022 in the same location as the dry bulb sensor. Connect the (2) 

wire gray harness with plug from the economizer to the enthalpy 

sensor.  See  wiring  diagram  Figures  23  and  28.  Refer  to  "9901-

2022 Outside Air Enthalpy Sensor” section for more details on 

enthalpy settings

Figure 5 – Connect Economizer Harness to Unit 

PL6 Economizer Harness

Step 8:

  Remove and save the 12-pin jumper plug from the unit 

economizer harness – located in the upper left corner of the unit. 

Insert the economizer plug into the unit wiring harness. See Figure 

5. 

Note: the 12-pin jumper plug should be saved for future use, in 

the event that the economizer is ever removed. The jumper plug is 

not needed as long as the economizer is installed.

Fig. 6 - Typical Indoor Fan Motor

Access Panel Locations

Indoor Blower

Access Panel

Unit Control

Box Panel(s)

Center Post

Step 10: 

In the hardware kit provided with the economizer is the 

9901-2020  Jade  controller  (Honeywell  W7220). The  controller  is 

attached to a mounting bracket and the economizer harness is 

attached to the controller. Mount the controller assembly on the 

left side of the unit control box. Screw bracket to the control box 

through pre-punched holes in control box. See Figure 7.

Figure 7 – Mount Controller Assembly in Unit 

Control Box

(Some control box configurations may differ)

 Step 11:

 Unplug the 10-pin female ECON plug currently connected 

to the Central Terminal Board (CTB). See Figure 8.

Rooftop Unit’s

12-Pin Male Plug

Economizer

12-Pin Female Plug

For 48/50LC 07-12 Instructions, see pages 10-12

Fig. 4 - Rear Economizer Flange Installation

(ECD-SRT12CA-D2*H and ECD-SRT34CA-D2*H)

Unit Filter 

Rack

Unit Base

Economizer

Hold Down Tab

Economizer Rear Flange

Economizer

Step 9:

 Remove the indoor blower access panel and the panel(s) 

covering the unit control box. See Figure 6. 

Summary of Contents for ECD-SRTCA-D2

Page 1: ...Foremost HVAC Accessory Manufacturer Economizer ECD SRTCA D2 Install Guide...

Page 2: ...Table of Contents Topic Page Number General 1 Topic Page Number General Install Instructions 1...

Page 3: ...ating the compressors when the outdoor air is too humid integrating the compressor with outdoor air when free cooling is available and locking out the compressor when outdoor air temperature is too co...

Page 4: ...581J 551J 04 06 549J 547J 559J 582J 04 06 548J 580J 558J 04 07 Dry Bulb OA Sensor ECD SRT12CA D2DH Enthalpy OA Sensor ECD SRT12CA D2EH Large Cabinet 581J 551J 07 12 580J 558J 08 14 548J 08 12 549J 07...

Page 5: ...California Energy Commission Title 24 prescriptive section 140 4 damper leakage etc and mandatory section 120 2 i for Fault Detection and Diagnostic controls Economizers meet ASHRAE 90 1 damper leaka...

Page 6: ...t wiring harness See Figure 5 Note the 12 pin jumper plug should be saved for future use in the event that the economizer is ever removed The jumper plug is not needed as long as the economizer is ins...

Page 7: ...ect 10 Pin Jade Plug to Central Terminal Board Figure 11 Connect Red and Brown Wires to Central Terminal Board Step 14 Connect the White wire from the Jade controller harness to the W1 terminal on the...

Page 8: ...he divider between the control box and the indoor blower section See Figure 14 Important See note below Figure 14 Route 9962 0407 SAOEXT Harness to Indoor Blower Section See note below Some control bo...

Page 9: ...rness See note For 48 50LC 07 12 Instructions see pages 10 12 Figure 17 Economizer Hood Assembly ECONOMIZER P N A B C D SHIP WT ECD SRT12CA D2 H 30 37 17 43 19 05 29 5 55 lb ECD SRT34CA D2 H 40 37 22...

Page 10: ...unit control box panel See Figure 6 Economizer performance charts are below See base unit installation manual to make adjustments to meet building ventilation requirements Economizer Hood Filter Door...

Page 11: ...W7220 JADE Controller Field Mounted in Unit Control Box MAT MAT OAT OAT ACT 24V ACT COM S BUS S BUS EXH1 IAQ COM ACT 2 10 AUX1 OUT IAQ 2 10 E GRD AUX2 IN Y1 IN Y1 OUT Y2 OUT Y2 IN OCC C R 10 Pin Femal...

Page 12: ...0LC 07 12 units only Figure 24 Remove Complete Harness Factory Attached to W7220 Controller Figure 24A 9962 0407 SAOEXT Not Used on 48 50LC 07 12 Units Note The complete 4 wire 9962 0407 SAOEXT harnes...

Page 13: ...indoor blower Confirm that the screws do not interfere with blower rotation See Figure 15 IMPORTANT The brown and orange wires in the indoor blower section for the mixed air sensor have spade terminal...

Page 14: ...trol box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220 controller from the Carrier factory is removed and not...

Page 15: ...2 sensor for outside air sensor the dipswitches on the sensor must be set to OFF OFF OFF See Table 8 The 2 gray wires with a plug from the economizer harness in the return chamber plug directly into t...

Page 16: ...ness Provided in 9901 2022 DIFF JC2 Kit DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZER OFF WHEN DESCRIPTION FIXED DRY BULB 1 3 5 11 16 OAT exceeds 75 F 2 4 10 OAT exceeds 73 F 6 8 9 OAT exce...

Page 17: ...90 1 require that the economizer s faults be accessible by operating or service personal or annunciated locally on zone thermostat To setup remote monitoring on the controller under SYSTEM SETUP AUX1...

Page 18: ...nical units is the Honeywell W7220 which is to be located in the RTU base unit s Control Box See Fig 35 for button description of the W7220 controller The W7220 controller provide the following 2 line...

Page 19: ...UT MIN POS The minimum position allows for ventilation even when not in the free cooling mode If you have a single speed unit there will be only one minimum position setting The default is 2 8 volts b...

Page 20: ...sensor is connected and displays measured discharge temperature Displays if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMP...

Page 21: ...ected Setpoint for Demand Control Ventilation of space Above the setpoint the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint MIN POS 2 8 V 2 t...

Page 22: ...3000 ppm Increment by 50 CO2 ppm span to match CO2 sensor STG3 DLY 2 0h 0 min 5 min 15 min then 15 min intervals Up to 4 h or OFF COOLING STAGE 3 DELAY Delay after stage 2 for cool has been active Tu...

Page 23: ...0 terminal provides 24 Vac out ACT UNDER V n a n a ACTUATOR VOLTAGE LOW Voltage received at actuator is below expected range ACT OVER V n a n a ACTUATOR VOLTAGE HIGH Voltage received at actuator is ab...

Page 24: ...c Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source ACT 2 10 2 10 Vdc Damper Actuator Output 2 10 Vdc ACT COM COM Damper Act...

Page 25: ...command dry bulb outdoor enthalpy differential dry bulb or differential enthalpy a call for cooling Y1 closes at the thermostat will cause the economizer control to modulate the dampers open and close...

Page 26: ...to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always illuminated What is a good setpoint for the Mixed Air Tempera ture MA...

Reviews: