PROGRAMMING THE JADE W7220 

CONTROLLER

The  next  several  pages  detail  the  different  status  displays, 

setpoints, setup, and alarms available on the controller. This list 

below and Table 10 summarizes the inputs required for a standard 

application with a single outside air sensor. 

NOTE:  instead  of 

setting the SETPOINTS you can use the 

defaults

 already set in 

the Jade controller – see 

default

 settings below. 

See Table 10 for 

summerized standard settings or for more detail see Table 11 – 

Menu Structure.

SETPOINTS

‒  MAT SET: this sets the mixed air temperature (MAT) setting. 

The controller has a default of 53 degrees, but the range is 

anywhere from 38 to 70 degrees F.

‒  LOW  T  LOCK:  This  setting  locks  out  the  compressor  (or 

mechanical cooling) at a given temperature. The default is 32 

degrees F, but the controller’s range is from -45 to 80 degrees 

F. 

‒  DRYBULB  SET:  if  you  have  an  economizer  with  a  dry  bulb 

outside air sensor you will see and set the DRYBULB SET. The 

default setting is 63 degrees F but the controller’s range is 48 

to 80 degrees F.  

‒  ENTH CURVE: if you have a single enthalpy outside air sensor 

instead of a dry bulb, you will see and set the ENTH CURVE 

setting. There are 5 setting options: ES1 thru ES5. Check the 

economizer literature for the limits for each of these settings. 

ES3 is the default setting.

SYSTEM SETUP

‒  INSTALL: Allows you to set the current date. Use the keypad 

buttons to scroll to the correct date.

‒  EQUIPMENT: Always set to CONV even if the unit is a heat 

pump.

‒  AUX2 IN: Always set to W1.

‒  FAN TYPE: Set for either single or 2 speed. The default is 2 

speed.

‒  AUX1 OUT: If remote Fault Detection and Diagnostic (FDD) 

monitoring is required select SYS. 

‒  OCC: occupancy, always set to INPUT

‒  MIN POS: The minimum position allows for ventilation even 

when not in the free-cooling mode. If you have a single speed 

unit  there will be only one minimum position setting. The 

default is 2.8 volts, but the range is 2-10Vdc.

  o  MIN POS H and MIN POS L: If your unit is 2 speed, there 

will be 2 minimum position settings that show up on the menu. 

The first is MIN POS H (for high speed) which has a default of 

2.8 volts. The second is MIN POS L (for low speed), which has 

a default of 3.2. 

Note that MIN POS H and MIN POS L are only 

displayed if under SYSTEM SETUP: AUX2 IN is set to “W1”, 

and FAN TYPE is set to 2 speed.

FOR SINGLE SPEED UNIT

FOR 2 SPEED UNITS

Controller Menu

Item

Default

Set To:

Default

Set To:

Note

SETPOINTS

MAT SET

53°F

38° to 70°F

53°F

38° to 70°F

LOW T LOCK

32°F

-45° to 80°F

32°F

-45° to 80°F

DRYBLB SET

63°F

48° to 80°F

63°F

48° to 80°F

Only displayed if using single DB OA sensor

ENTH CURVE

ES3

ES1 to ES5

ES3

ES1 to ES5

Only displayed if using a single enthalpy OA sensor

MIN POS

2.8 Vdc

2 to 10 Vdc

NA

Only displayed if set up for single speed unit

MIN POS H

NA

NA

2.8 Vdc

2 to 10 Vdc

Only displayed if set up for 2 speed unit

MIN POS L

NA

NA

3.2 Vdc

2 to 10 Vdc

Only displayed if set up for 2 speed unit

SYSTEM SETUP

INSTALL

1/1/2010

Current date

1/1/2010

Current date

EQUIPMENT

CONV

CONV

CONV

CONV

Always set to CONV, even on HP units

AUX2 I

W1*

W1

W1*

W1

Always set to W1

FAN TYPE

2 speed*

1 speed

2 speed*

2 speed

Default may vary on some models

AUX1 OUT

NONE

SYS

NONE

SYS

Set to SYS for remote FDD monitoring

OCC

INPUT

INPUT

INPUT

INPUT

Always set to INPUT

Table 10 - Standard Jade W7220 Controller Configuration

Note 1:

 For 2 speed unit, under SYSTEM SETUP: EQUIPMENT= 

CONV, AUX2 I = W1, and FAN TYPE = 2 SPEED

Note 2:

 More sophisticated controller setups, including for DCV or power exhaust, are available by referring to Table 11 options

NA = Not applicable
*Available on Firmware 1.15 June 2018 and later

Summary of Contents for ECD-SRTCA-D2

Page 1: ...Foremost HVAC Accessory Manufacturer Economizer ECD SRTCA D2 Install Guide...

Page 2: ...Table of Contents Topic Page Number General 1 Topic Page Number General Install Instructions 1...

Page 3: ...ating the compressors when the outdoor air is too humid integrating the compressor with outdoor air when free cooling is available and locking out the compressor when outdoor air temperature is too co...

Page 4: ...581J 551J 04 06 549J 547J 559J 582J 04 06 548J 580J 558J 04 07 Dry Bulb OA Sensor ECD SRT12CA D2DH Enthalpy OA Sensor ECD SRT12CA D2EH Large Cabinet 581J 551J 07 12 580J 558J 08 14 548J 08 12 549J 07...

Page 5: ...California Energy Commission Title 24 prescriptive section 140 4 damper leakage etc and mandatory section 120 2 i for Fault Detection and Diagnostic controls Economizers meet ASHRAE 90 1 damper leaka...

Page 6: ...t wiring harness See Figure 5 Note the 12 pin jumper plug should be saved for future use in the event that the economizer is ever removed The jumper plug is not needed as long as the economizer is ins...

Page 7: ...ect 10 Pin Jade Plug to Central Terminal Board Figure 11 Connect Red and Brown Wires to Central Terminal Board Step 14 Connect the White wire from the Jade controller harness to the W1 terminal on the...

Page 8: ...he divider between the control box and the indoor blower section See Figure 14 Important See note below Figure 14 Route 9962 0407 SAOEXT Harness to Indoor Blower Section See note below Some control bo...

Page 9: ...rness See note For 48 50LC 07 12 Instructions see pages 10 12 Figure 17 Economizer Hood Assembly ECONOMIZER P N A B C D SHIP WT ECD SRT12CA D2 H 30 37 17 43 19 05 29 5 55 lb ECD SRT34CA D2 H 40 37 22...

Page 10: ...unit control box panel See Figure 6 Economizer performance charts are below See base unit installation manual to make adjustments to meet building ventilation requirements Economizer Hood Filter Door...

Page 11: ...W7220 JADE Controller Field Mounted in Unit Control Box MAT MAT OAT OAT ACT 24V ACT COM S BUS S BUS EXH1 IAQ COM ACT 2 10 AUX1 OUT IAQ 2 10 E GRD AUX2 IN Y1 IN Y1 OUT Y2 OUT Y2 IN OCC C R 10 Pin Femal...

Page 12: ...0LC 07 12 units only Figure 24 Remove Complete Harness Factory Attached to W7220 Controller Figure 24A 9962 0407 SAOEXT Not Used on 48 50LC 07 12 Units Note The complete 4 wire 9962 0407 SAOEXT harnes...

Page 13: ...indoor blower Confirm that the screws do not interfere with blower rotation See Figure 15 IMPORTANT The brown and orange wires in the indoor blower section for the mixed air sensor have spade terminal...

Page 14: ...trol box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220 controller from the Carrier factory is removed and not...

Page 15: ...2 sensor for outside air sensor the dipswitches on the sensor must be set to OFF OFF OFF See Table 8 The 2 gray wires with a plug from the economizer harness in the return chamber plug directly into t...

Page 16: ...ness Provided in 9901 2022 DIFF JC2 Kit DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZER OFF WHEN DESCRIPTION FIXED DRY BULB 1 3 5 11 16 OAT exceeds 75 F 2 4 10 OAT exceeds 73 F 6 8 9 OAT exce...

Page 17: ...90 1 require that the economizer s faults be accessible by operating or service personal or annunciated locally on zone thermostat To setup remote monitoring on the controller under SYSTEM SETUP AUX1...

Page 18: ...nical units is the Honeywell W7220 which is to be located in the RTU base unit s Control Box See Fig 35 for button description of the W7220 controller The W7220 controller provide the following 2 line...

Page 19: ...UT MIN POS The minimum position allows for ventilation even when not in the free cooling mode If you have a single speed unit there will be only one minimum position setting The default is 2 8 volts b...

Page 20: ...sensor is connected and displays measured discharge temperature Displays if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMP...

Page 21: ...ected Setpoint for Demand Control Ventilation of space Above the setpoint the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint MIN POS 2 8 V 2 t...

Page 22: ...3000 ppm Increment by 50 CO2 ppm span to match CO2 sensor STG3 DLY 2 0h 0 min 5 min 15 min then 15 min intervals Up to 4 h or OFF COOLING STAGE 3 DELAY Delay after stage 2 for cool has been active Tu...

Page 23: ...0 terminal provides 24 Vac out ACT UNDER V n a n a ACTUATOR VOLTAGE LOW Voltage received at actuator is below expected range ACT OVER V n a n a ACTUATOR VOLTAGE HIGH Voltage received at actuator is ab...

Page 24: ...c Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source ACT 2 10 2 10 Vdc Damper Actuator Output 2 10 Vdc ACT COM COM Damper Act...

Page 25: ...command dry bulb outdoor enthalpy differential dry bulb or differential enthalpy a call for cooling Y1 closes at the thermostat will cause the economizer control to modulate the dampers open and close...

Page 26: ...to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always illuminated What is a good setpoint for the Mixed Air Tempera ture MA...

Reviews: