Operation
Refer to the table below for single and two stage options for alarm tones.
Temporal
0.5 second on, 0.5 second off, 0.5 second on, 0.5 second off, 0.5 second on, 1.5 second off,
then repeat.
Alert Code
0.5 second on 2.5 seconds off, then repeat
Figure 33 Temporal and Alert Alarm Code
7.1.7 Button Operation while in Alarm Condition (UL)
Pressing the button while the Wireless Input/Output unit is in alarm condition has no effect on
the Wireless Input/Output unit. This is the default operation.
7.1.8 Button Operation while in Alarm Condition (ULC Dwelling Unit Use Only)
This ULC operation must be configured, default is UL operation. Pressing the Wireless Input/
Output unit button while the Wireless Input/Output unit is in alarm condition silences the horn
or strobe for 10 minutes and turns the LEDs steady red. After the 10 minute period has
elapsed, the Wireless Input/Output unit re-activates the horn or strobe at its nominal volume
and at the tone it was set to by the alarm.