22
Wiring
5.3
Zone Controller Relay Wiring to FACP Input Zones
Figure 24 Wiring From Zone Controllers to Conventional FACP
5.4
FACP SLC Loop Wiring to Zone Controllers
Figure 25 shows SLC Class B wiring with the MIX-M500MAP(A) Advanced Protocol
addressable input monitor module and MIX-M500RAP(A) Advanced Protocol addressable
relay output module. When an alarm occurs, the Fire Alarm Control Panel activates the relay
module, and the Zone Controller’s input detects that the relay module is activated. The Zone
Controller then activates the Wireless Input/Output units, which activates the notification
appliances.
In the case of a trouble on the Zone Controller, the Zone Controller activates its Output, which
activates the input module, which then sends a signal to the Fire Alarm Control Panel. Since
the Zone Controller has 4 Outputs, this application can provide up to 4 different types of
trouble, or 1 alarm and up to 3 different types of trouble.
NOTE:
If the fire alarm control panel has off premise signalling, one of the Zone Controller
Outputs must be programmed for AC trouble.
Zone
Controller 1
FACP
Zone
Controller 16
Output
Output
NO
C
NC
NO
C
NC
47K EOL
Input Zone 1
Input Zone 16
47K EOL
Trouble
Trouble
Use UL listed EOL resistors
Summary of Contents for Fire-Link 3