WORKING DETAILS AND EXPLANATIONS 

The first config step is to set the type of system to be monitored on 

P01 “Voltage”

 (default = 3PH 400). 

If the default values are kept as they are, here is the explanation of the different working situations: 

Mains KO 

- After the delay set in 

P07 

“Genset start delay” 

(default = 5s): 

Contact GEN. RUN  = ON 

(contact closed) 

- After the delay set in 

P08 

“Delay Genset OK” 

(default = 120s) + time set in 

P09 

“Mains/Genset delay” 

(default = 5s): 

Contact TM  = OFF  (contact open) 

- After the delay set in 

P19 

“Commutation delay” 

(default = 500ms)

 

Contact TG  = ON 

(contact closed, load on Generator) 

Genset OK + Mains OK 

- After the delay set in 

P10 

“Genset/Mains delay” 

(default = 10s): 

Contact TG  = OFF  (contact open) 

- After the delay set in 

P19 “Commutation delay” 

(default = 500ms)

 

Contact TM  = ON 

(contact closed, load on Mains) 

- After the delay set in 

P11 

“Genset off delay” 

(default = 30s): 

Contact GEN. 

RUN 

= OFF  (contact open) 

Mains KO + Genset KO + P18 (OFF): 

Contact TM  = OFF  (contact open) 

 

 

 

 

 

 

 

Contact TG  = ON 

(contact closed) 

Relay ALARM  = ON 

(contact closed) 

 
 

ERRORS - 

P18 “Genset/Mains forced”

 (default = OFF)

 

If disabled, every time an error occurs, the Genset will be switch-off and the device will remain on Genset source. 

If enabled, every time an error occurs, the Genset will be switch-off and the device will automatically commute on 
Mains source. 
The error sign on the device is not cancelled until the problem on the Gen is not solved. 

Then it is possible to press 

 

(SET)

 

and make the error sign disappear. 

 

Max or Min Mains Voltage Error. 

It is indicated as 

“HIGH”

 (max) o 

“LOW”

 (min) in the proper section of the display (pag. 3  

“ERROR”). 

The device starts the changeover sequence: 

1) Genset ignition. 

2) Genset voltages and frequency check. 

3) Changeover from Mains to Genset. 

The  verification  time  of  voltage  and  frequency  is  set  in 

P08 

“Delay  Genset  OK” 

(default  =  120s),  beyond 

this, the display will show error 

“Er1/Er2”

The changeover will happen only when the Genset parameters will be validated. 

On Genset as source, when the parameters are out of the limits, the display will show:

“Er1”:

 Genset voltage out of limits, set in 

P05

 

Min. Genset voltage

” 

(default = -10%) and in 

P

06 “Max. 

Genset voltage

” 

(default = +10%).

“Er2”:

 Genset frequency out of limits, set in 

P12 

“Frequency tolerance”

 (default = ±5Hz). 

 

Summary of Contents for EVO DTS-B

Page 1: ...i de ntre inere asupra dispozitivului ndep rta i toate tensiunile de la intr rile de m surare i de alimentare i scurtcircuita i bornele de intrare CT Produc torul nu poate fi considerat responsabil pe...

Page 2: ...microidea it Web www microidea it TYPICAL WIRING DIAGRAM for reference purposes only The installation has to be equipped with an external disconnection device that should be easily reachable and iden...

Page 3: ...ternatively from Auto and Mode Using the P13 Working mode default MAN we can define the default mode we can also lock this working mode by using the P14 Working mode lock default OFF The transition fr...

Page 4: ...repeat the sequence if you need to modify others To exit this menu press for 3s the key EXIT 6 You will be prompted for Save parameters then press key YES or NO 1 2 3 4 5 6 FACTORY RESET default para...

Page 5: ...10 Genset Mains delay s 1 240 Delay between stable Mains and Genset changeover 10 P11 Genset off delay s 1 240 Delay time between changeover and Genset switch off 30 P12 Frequency tolerance Hz 1 9 Fre...

Page 6: ...firm or NO to cancel The changeover is confirmed by the Genset image from the contact symbol closed wich confirms the contactor bobbin activation LG and from the voltage and frequency background colou...

Page 7: ...ON contact closed Relay ALARM ON contact closed ERRORS P18 Genset Mains forced default OFF If disabled every time an error occurs the Genset will be switch off and the device will remain on Genset sou...

Page 8: ...filter default 1s the display will show Er4 Phase asymmetry of the Genset beyond limits set in P20 PH asymmetry tolerance default 20V Missing Voltage Error or Contactor malfunction only DTS E model Th...

Page 9: ...ET 2 Press key to set the value to ON then press SET to confirm and access the PASSWORD screen where you will be asked to insert the actual password if this is the first time leave the value default 0...

Page 10: ...ntactor coil 5A 250V TG Genset contactor coil 5A 250V Alarm Relay Output Max current 8A Max voltage 250V Electrical contact Life 100 x 103 ops Mechanical contact Life 30 x 103 ops Ambient conditions O...

Page 11: ...11 12 ITALY Tel 39 035 773 925 Fax 39 035 773 e mail microidea microidea it Web www microidea it BACK PANEL CONNECTIONS DIMENSIONS Only for DTS E model...

Page 12: ...12 12 ITALY Tel 39 035 773 925 Fax 39 035 773 e mail microidea microidea it Web www microidea it...

Reviews: