MICROIDEA EVO DTS-B User And Installation Manual Download Page 5

5 / 12 

 

- ITALY - Tel. +39.035.773 925 - Fax +39.035.773 - e-mail: [email protected] - Web: www.microidea.it 

 

PARAMETERS TABLE 

PAR. 

FUNZIONE 

UM 

VALORI 

DESCRIZIONE

DEFAULT 

P0A 

Language 

ITA / ENG 

Device language (English, italian). 

ENG 

P0B 

Contrast display 

0

…25 

Display contrast settings. 

P0C 

Password 

OFF / ON 

If ON allows to choose a numeric password of 4 digits. 
Default value is 0000. 

OFF 

P01 

Voltage 

V

 

1PH 208 / 3PH 208  
1PH 230 / 3PH 230 
1PH 400 / 3PH 400 
1PH 440 / 3PH 440 

Connection type and voltage to monitor. 

3PH 400 

P02 

Frequency 

Hz 

50 / 60 

Nominal Frequency.

 

50 

P03 

Min. Mains voltage 

V

 

-

1…-20 

Lower Mains voltage limit.

 

-10 

P04 

Max. Mains voltage 

V

 

+1…+20 

Higher Mains voltage limit.

 

+10 

P05 

Min. Genset voltage 

-

1…-20 

Lower Genset voltage limit.

 

-10 

P06 

Max. Genset voltage 

+1…+20 

Higher Genset voltage limit. 

+10 

P07 

Genset start delay 

1…600 

Changeover  delay  between  the  error  identification  on  the 
Mains and turning ON the Genset.

 

 

P08 

Delay Genset OK 

1…600 

Time limit within the Genset has to fit the assigned values. 
Once values are reached the time resets.

 

120 

P09 

Mains/Genset delay 

1…240 

Changeover  delay  between  Genset  OK  and  the  change 
between Mains to Genset.

 

 

P10 

Genset/Mains delay 

1…240 

Delay between stable Mains and Genset changeover.

 

10 

P11 

Genset off delay 

1…240 

Delay time between changeover and Genset switch-off.

 

30 

P12 

Frequency tolerance 

±Hz 

1…9 

Frequency tolerance on Genset.

 

P13 

Working mode 

MAN / AUT 

Working mode on switch-on.

 

MAN 

P14 

Working mode lock

 

ON / OFF 

Working mode lock.

 

OFF 

P15 

Error mask 

0…60 

Filter  mask  to  avoid  false  positive  due  to  the  transition 
between Genset and the connected load.

 

P16 

Attempts to 
reconnection 

0…20 

Number of reconnection attempts after an error. 

P17 

Reconnect delay 

10…900 

Delay before reconnection attempts (see P16). 

120 

P18 

Genset/Mains forced

 

ON / OFF 

If  enabled,  forces  the  changeover  back  to  Mains  if  the 
Genset, due to a malfunction, switch-off.

 

OFF 

P19 

Commutation delay 

TM / TG

 

ms 

250…2500 

Interlocking delay between Mains/Genset or vice versa. 

500 

 
 

DTS-E version only: 

P20 

PH asymmetry 
tolerance 

only 3PH system 

V

 

10…40 

Tolerance value on phases asymmetry.

20 

P21 

PH asymmetry 
tolerance filter 

only 3PH system

 

1…30 

Delay  between  asymmetry  condition  detected  and  the  error 
notification on display.

P22 

Alarm relay 

NO / NC / OFF 

If enabled, the relay activates on every error. 
The settings refer to relay on rest. 

NO 

P23 

Contactors control 

OFF 

LM-LG / AM-AG 

Inputs to be monitored, coils or aux contacts. 
In case of errors the display will show “Er3”

OFF 

 

 

Summary of Contents for EVO DTS-B

Page 1: ...i de ntre inere asupra dispozitivului ndep rta i toate tensiunile de la intr rile de m surare i de alimentare i scurtcircuita i bornele de intrare CT Produc torul nu poate fi considerat responsabil pe...

Page 2: ...microidea it Web www microidea it TYPICAL WIRING DIAGRAM for reference purposes only The installation has to be equipped with an external disconnection device that should be easily reachable and iden...

Page 3: ...ternatively from Auto and Mode Using the P13 Working mode default MAN we can define the default mode we can also lock this working mode by using the P14 Working mode lock default OFF The transition fr...

Page 4: ...repeat the sequence if you need to modify others To exit this menu press for 3s the key EXIT 6 You will be prompted for Save parameters then press key YES or NO 1 2 3 4 5 6 FACTORY RESET default para...

Page 5: ...10 Genset Mains delay s 1 240 Delay between stable Mains and Genset changeover 10 P11 Genset off delay s 1 240 Delay time between changeover and Genset switch off 30 P12 Frequency tolerance Hz 1 9 Fre...

Page 6: ...firm or NO to cancel The changeover is confirmed by the Genset image from the contact symbol closed wich confirms the contactor bobbin activation LG and from the voltage and frequency background colou...

Page 7: ...ON contact closed Relay ALARM ON contact closed ERRORS P18 Genset Mains forced default OFF If disabled every time an error occurs the Genset will be switch off and the device will remain on Genset sou...

Page 8: ...filter default 1s the display will show Er4 Phase asymmetry of the Genset beyond limits set in P20 PH asymmetry tolerance default 20V Missing Voltage Error or Contactor malfunction only DTS E model Th...

Page 9: ...ET 2 Press key to set the value to ON then press SET to confirm and access the PASSWORD screen where you will be asked to insert the actual password if this is the first time leave the value default 0...

Page 10: ...ntactor coil 5A 250V TG Genset contactor coil 5A 250V Alarm Relay Output Max current 8A Max voltage 250V Electrical contact Life 100 x 103 ops Mechanical contact Life 30 x 103 ops Ambient conditions O...

Page 11: ...11 12 ITALY Tel 39 035 773 925 Fax 39 035 773 e mail microidea microidea it Web www microidea it BACK PANEL CONNECTIONS DIMENSIONS Only for DTS E model...

Page 12: ...12 12 ITALY Tel 39 035 773 925 Fax 39 035 773 e mail microidea microidea it Web www microidea it...

Reviews: