TECHNICAL DATA
Supply
Voltage
9
…36V
Operating limits
-
10%…+10% Ue
Power Consumption (at 36V)
1W
Meausurement/Overvoltage category
Class II
Measures and monitoring range
Connection type and voltage V
1PH 208 / 3PH 208
1PH 230 / 3PH 230
1PH 400 / 3PH 400
1PH 440 / 3PH 440
Frequency
50 / 60Hz
Genset voltage range
0…500V
Mains voltage range
0…500V
Measures precision
± 2%
-AG/+AG | - AM/+AM (aux contacts rating)
9
…36V
Start Gen rating contact
5A -
10…30V
TM - Mains contactor coil
5A - 250V
TG - Genset
c
ontactor coil
5A - 250V
Alarm Relay Output
Max current
8A
Max voltage
250V
Electrical contact Life
100 x 10
3
ops
Mechanical contact Life
30 x 10
3
ops
Ambient conditions
Operating temperature
-20 / +50 °C
Storage temperature
-30 / +70 °C
Operating altitude
up to 2000m
Maximum pollution degree
2
Relative Humidity w/o condensation
90 RH%
Connections and Housing
Type of terminal
Pluggable
Conductor cable type
only 105°C - 1.5/2.5mm
2
- 16/14 AWG
Enclosure version
Flush Mount
Protection degree
IP41 Front - IP20 Terminals
Dimensions
96 x 96 x 70mm
Weight
360g
EC Directives:
- 2014/30/UE - EMC
- 2014/35/UE - LVD
LATENCY TIME
The control device monitors up to 6 voltages, therefore the Max latency time between each measure is 2s.