MC40-SEF
Doc. N°
MO-0475-ING
Copyright 2012
FW: 1320.38.01.x
Date
06.09.2022
Rev.
1
Pag.
29
of
36
12.5.4 - Function (Functions)
“Function”
,
1
st
function,
to scroll available Functions,
to Read/Write setting of the selected function,
to select the different definable fields
-
FuncEnab
-
TripLev
-
Options
-
Timers
to access the selected field and read the actual
setting of the relevant variable
to modify the actual setting;
to set the new value.
to validate.
Set Done!
Display
Description
Setting Range
Step
Function
Type
Variable
Default
Setting
Unit
Password
= 0000-9999
1111
-
Password for programming enable (see § Password)
T>
(F49)
FuncEnab
→
Disable
Enable of the protection function
Enable/Disable
-
Options
→
NoParam
No Parameters
-
-
TripLev
→
Tal
50
%Tb
Thermal prealarm
50 - 110
1
Tst
100
%Tb
Reset level.
10 - 100
1
Timers
→
NoParam
No Parameters
-
-
I>
(1F51)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
TCC
D
Time Current Curves
D,A,B,C, I, VI,
EI, MI, SI
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
I>
0.5
In
Trip level of overcurrent protection
0.20
–
4.00
0.01
Timers
→
tI>
2.00
s
Trip time delay
0.05
–
60.00
0.01
I>>
(2F51)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
2xI
Disable
Automatic threshold doubling on inrush
Enable/Disable
-
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
I>>
2.00
In
Trip level of overcurrent protection
0.50
–
40.00
0.01
Timers
→
tI>>
1.00
s
Trip time delay
0.05
–
60.00
0.01
t2x I
0.01
s
Trip time delay Automatic threshold doubling
0.02
–
9.99
0.01
IH
(3F51)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
2xI
Enable
Automatic threshold doubling on inrush
Enable/Disable
-
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
IH
5.00
In
Trip level of overcurrent protection
0.50
–
40.00
0.01
Timers
→
tIH
0.05
s
Trip time delay
0.05
–
60.00
0.01
t2xI
0.10
s
Trip time delay Automatic threshold doubling
0.02
–
9.99
0.01
Io>
(1F51N)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
TCC
D
Time Current Curves
D,A,B,C, I, VI,
EI, MI, SI
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
Io>
0.10
Ion
Trip level of Earth Fault protection
0.01
–
4.00
0.01
Timers
→
tIo>
2.00
s
Trip time delay
0.05
–
60.00
0.01
Io>>
(2F51N)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
Io>>
0.50
Ion
Trip level of Earth Fault protection
0.01
–
9.99
0.01
Timers
→
tIo>>
1.00
s
Trip time delay
0.05
–
60.00
0.01