MC40-SEF
Doc. N°
MO-0475-ING
Copyright 2012
FW: 1320.38.01.x
Date
06.09.2022
Rev.
1
Pag.
27
of
36
12.4 - LastTrip (Event Recording)
The MC records any tripping and stores the information relevant to the last 20 tripping of protection functions
(FIFO). Each event recording includes the following information.
“
Re
al Time Meas”
“LastTrip”
1
st
event,
to scroll available events,
to “Rec #”
selected,
to select the different fields;
Display
Description
Func
xxxxx
Indication of the protection function which caused the relay tripping.
For indication of the TRIP Cause the following acronyms are used:
T>
= Thermal Image
I>
= 1
st
Overcurrent (Short Circuit)
I>>
= 2
nd
Overcurrent (Short Circuit)
IH
= 3
rd
Overcurrent (Short Circuit)
Io>
= 1
st
Neutral Element
Io>>
= 2
nd
Neutral Element
IoH
= 3
rd
Neutral Element
So>
= Sensitive Neutral Element
RTD
= External Trip commands
IRF
= Internal Relay Fault
Date
: YYYY/MM/GG
Date: Year/Month/Day
Time
: hh:mm:ss:cc
Time: hours/minutes/second/hundredths of seconds
IA
= 0
–
65535
A
RMS value of phase A current (Primary Amps)
IB
= 0
–
65535
A
RMS value of phase B current (Primary Amps)
IC
= 0
–
65535
A
RMS value of phase C current (Primary Amps)
Io
= 0.0
–
6553.5 A
RMS value of Zero Sequence Current (Primary Amps)
Tem
= 0 - 65535
%T Actual temperature rise
to go back to “Rec #”
,
to go back to “Real Time Meas”
.