3.3 - I>> (2F51) - Second overcurrent protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
2xI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
I>>
2.00
In
(0.50
40.00)
step 0.01
In
Timers
→
tI>>
1.00
s
(0.05
60.00)
step
0.01
s
→
t2xI
0.10
s
(0.02
9.99)
step
0.01
s
Description of variables
FuncEnab
: If disable the function is deactivated
BI
: Operation controlled by Blocking Digital Input
2xI
: Automatic threshold doubling on inrush
Trg
: Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
I>>
: Trip level (limited to 40 times In)
tI>>
: Trip time delay
t2xI
: Trip time delay
Trip when
: The
current trip level is exceeded for time “tI>>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
= Is recorded
Function reset when
: The current drop below 95% I>>.
Led reset when
: push-button is pressed