18.4.2 - Functions - Operation Mode
Automatic
: In this mode the output relay is “
operated
” (energized if “
N.D.
”, denergized if “
N.E.
”)
when the controlling Functional Output is activated and it is reset to the “non operated”
condition when the Functional Output gets disactivated but, anyhow, not before the time
“
tON
” has elapsed (minimum duration of the operation time)
Manual
: In this mode the output relay is “
operated
” when the controlling Functional Output is
activated and remains in the operated condition until a manual reset command is issued
by the relay keyboard (local commands menu) or via the serial communication. In this
mode the timer “
tON
” has no effect.
Impulsive
: In this mode the output relay is “
operated
” when the controlling Functional Output is
activated and it remains in the “
operated
” condition (energized if “
N.D.
”, denergized if
“
N.E.
”) for the set time “
tON
” independently from the status of the controlling Functional
Output.
Open software program and connect to the relay.
Select “
Change Windows
” from “
Menu
”
Select “
DO Configuration
”