MC2-30T
Doc. N°
MO-0483-ING
Copyright 2016
Date
17.03.2022
Rev.
2
Pag. 43
of
70
17.15 - Function:
Reclos
(Automatic Reclosure RCL)
Status
→
Enab.
Yes
[No / Yes]
Options
→
ShNum
1
[0 - 1 - 2 - 3 - 4]
→
R 1I>
1+2+3+4
→
Recl. Dis = Automatic Reclosure (AR) disable
1
= AR Enable on shot 1
2
= AR Enable on shot 2
1+2
= AR Enable on shot 1+2
3
= AR Enable on shot 3
1+3
= AR Enable on shot 1+3
2+3
= AR Enable on shot 2+3
1+2+3
= AR Enable on shot 1+2+3
4
= AR Enable on shot 4
1+4
= AR Enable on shot 1+4
2+4
= AR Enable on shot 2+4
1+2+4
= AR Enable on shot 1+2+4
3+4
= AR Enable on shot 3+4
1+3+4
= AR Enable on shot 1+3+4
2+3+4
= AR Enable on shot 2+3+4
1+2+3+4 = AR Enable on shot 1+2+3+4
(*) see example
→
R 2I>
1+2+3+4
Same as above
→
R 3I>
1+2+3+4
Same as above
→
R 1Io>
1+2+3+4
Same as above
→
R 2Io>
1+2+3+4
Same as above
→
R 3Io>
Recl. Dis.
Same as above
→
GR1-2
Disable
[Disable / Shot1 / Shot2 / Shot3 / Shot4]
→
SeqC
Disable
[Disable / Enable]
Timers
→
tSeqC
0
s
(0.00
÷
5.00)
step
0.01 s
→
t1
2
s
(0.10
÷
200)
step
0.1
s
→
Tr1
5
s
(5.00
÷
200)
step
1
s
→
Td1
0
s
(0.00
÷
5.00)
step
0.1
s
→
t2
4
s
(0.10
÷
1000)
step
0.1
s
→
Tr2
5
s
(5.00
÷
200)
step
1
s
→
Td2
0
s
(0.00
÷
5.00)
step
0.1
s
→
t3
6
s
(0.10
÷
1000)
step
0.1
s
→
Tr3
5
s
(5.00
÷
200)
step
1
s
→
Td3
0
s
(0.00
÷
5.00)
step
0.1
s
→
t4
8
s
(0.10
÷
1000)
step
0.1
s
→
Tr4
5
s
(5.00
÷
200)
step
1
s
→
TrCL
5
s
(5.00
÷
200)
step
1
s
→
ThExt
5
s
(5.00
÷
200)
step
1
s