MC2-30T
Doc. N°
MO-0483-ING
Copyright 2016
Date
17.03.2022
Rev.
2
Pag. 39
of
70
17.8 – Function:
2I>
(Second Overcurrent Element F50/51)
Status
→
Enab.
Yes
[No / Yes]
Options
→
tBI
Off
[Off / 2tBO]
→
2xI
Disable
[Disable / Enable]
Oper. Levels
→
Is
1
In
(0.1
÷
40)
step 0.01 In
Timers
→
ts
5
s
(0.02
÷
100)
step
0.01 s
→
tBO
0.75
s
(0.05
÷
0.75)
step
0.01 s
→
t2xI
2
s
(0.02
÷
100)
step
0.01 s
→
td2xI
0.06
Fixed
17.8.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
tBI
: Blocking input reset time
Off
= Permanent block
2tBO
= Set 2xtBO.
2xI
: Automatic doubling of trip level on inrush
Is
: Minimum operation level
ts
: Trip time delay
tBO
: Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
also the trip time delay of the Breaker Failure function.
t2xI
: Maximum time of automatic threshold doubling on inrush
td2xI
: Time for calculation of current rate of rise.
17.9 - Function:
3I>
(Third Overcurrent Element F50/51)
Status
→
Enab.
Yes
[No / Yes]
Options
→
tBI
Off
[Off / 2tBO]
→
2xI
Disable
[Disable / Enable]
Oper. Levels
→
Is
1
In
(0.1
÷
40)
step 0.01 In
Timers
→
ts
5
s
(0.02
÷
100)
step
0.01 s
→
tBO
0.75
s
(0.05
÷
0.75)
step
0.01 s
→
t2xI
2
s
(0.02
÷
100)
step
0.01 s
→
td2xI
0.06
Fixed
17.9.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
tBI
: Blocking input reset time
Off
= Permanent block
2tBO
= Set 2xtBO.
2xI
: Automatic doubling of trip level on inrush
Is
: Minimum operation level
ts
: Trip time delay
tBO
: Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
also the trip time delay of the Breaker Failure function.
t2xI
: Maximum time of automatic threshold doubling on inrush
td2xI
: Time for calculation of current rate of rise.