background image

24

USING THE TANK COUNTER

With the rotary switch in the TANK position, the left-hand 

display shows the amount remaining in the tank.  If a FILL 

TANK SIZE (tank full) number  has been entered in Special 

Calibration, the “AUTO FILL” feature is active; this feature 

allows the TANK counter to be quickly reset to a full tank 

amount by simply pressing the “+” button with the rotary 

switch in the TANK position.  The “-” button can be used to 

reduce the tank counter, but any press of the “+” will set the 

counter to the calibrated FILL TANK SIZE value. 
If no TANK VALUE has been entered in calibration, the tank 

counter can still be used, but the counter must be manually 

adjusted when filled, by pressing and holding the “+” 

button until the desired value is reached. 

WARNING DEVICE

The console is equipped with a RED warning light. The 

light will automatically turn on and flash when the actual 

application is plus or minus 10 percent of  the calibrated 

target rate, or if the TANK alarm feature is activated and 

the tank is below the set point (display will also flash “FILL” 

message).  If the light stays on while in AUTO, refer to the 

troubleshooting section of this manual. The RED warning 

light will also be illuminated when calibration mode is 

active on the console.

AUDIBLE ALARM

The Audible Alarm is activated for the following conditions:

• 

The calculated Tank level is below minimum level 

(TANK ALARM SET POINT).

• 

Float switch is continuously active for 15 seconds or 

more.

• 

The Application Rate Error is greater than 10% for 3 

seconds (continuously) after the Auto Delay and Start 

Up time have completed and the console is in AUTO, 

and the Ground Speed is above the Alarm Minimum 

Speed.

EMERGENCY STOP

When in AUTO and in RUN with one or more Booms on and 

the Speed is greater than zero, if the Flow signal ever stops, 

the servo will run to fully open.  If Flow remains stopped 

for 5 seconds or more, it will automatically reduce the flow 

to a minimum (run Servo for 4 seconds). “EStOP” will then 

display to notify the user of the Emergency Stop.  The flow 

remains off (or reduced) and AUTO control will remain 

disabled until the system goes into HOLD, power is cycled 

or CALIBRATE is entered.  The Emergency Stop feature helps 

protect against “chemical spills” or over-application if the 

Flow signal is lost.

TANK ALARM

If a TANK SET POINT (tank low) number has been entered 

in Special Calibration, the TANK ALARM feature is 

active.  When the tank counter value drops below the 

TANK SET POINT, the red warning light will flash and “FILL” 

will flash on the left-hand display.  The “FILL” message 

will flash no matter what position the rotary switch is 

in. Adjusting the tank value to a value greater than the 

SET POINT will turn the alarm off. 

WIDTH

CAL

FLOW

CAL

MIN

FLOW

ADJUST

RATE

TARGET

RATE

SPEED

CAL

INLINE

BYPASS

TEST

SPEED

VOLUME /

MINUTE

DISTANCE

AREA /

HOUR

VOLUME

(1) (2) (3)

RATE

SPEED

AREA

(1) (2) (3)

ON

OFF

1

2

3

4

5

B O O M S

RUN

HOLD

CAL

AUTO

MAN

RESET

ON / OFF

____

APPLICATION RATE

TANK

___

Operation 

(cont)

Automatic Operation 

(cont)

In TANK position, press”+” to 

enter full tank amount.

Rotary Switch Positions

(See the NH3 section in the Appendix for NH3 data 

description.)

RATE

Actual number of gallons per acre (liters per hectare) being 

applied.

TANK

Amount (gal or lit) remaining in tank.

VOLUME/MINUTE

Flow rate in GPM (LPM).
Three independent pairs of counters.  In either the AREA 

or the VOLUME position, select a  pair of counters by 

pressing the “+” button.  The active pair of counters (1,2,3) is 

indicated by the small numbers in the lower right corner of 

the left-hand display.  DO NOT attempt to select the counter 

pair by using the “-” button because it 

will reset the selected counter pair to 

zero.  See additional data description 

below and see RESETTING SYSTEM COUNTERS section.

VOLUME (1) (2) (3)

Total gallons (liters) applied since the active counter was 

last reset to zero.

AREA (1) (2) (3)

The acres (hectares) covered since the counter was last reset 

to zero.  The area counters do not accumulate area when 

the console is in HOLD or if all booms are turned OFF.

DISTANCE

The feet (meters) driven since the counter was last reset to 

zero.  This counter does not accumulate when the console is 

in HOLD.  This counter may be reset to zero independent of 

other system counters.

AREA/HOUR

Rate of coverage in acres/hour (hectare/hour).

SPEED

Ground speed in miles (kilometers) per hour.  IMPORTANT: 

all booms automatically shut off if system is in “HOLD” or if 

in AUTO with NO SPEED.

SEEDS (1) (2) (3):

AREA (1) (2) (3):

)

Summary of Contents for MT-3405F II

Page 1: ...MT 3405F II Dual Display Automatic Rate Controller Reference Manual...

Page 2: ...o fa mil iar ize yourself with this manual and the system components before beginning Following the procedures described in this manual will ensure proper per for mance and help avoid problems in the...

Page 3: ...rvices if any all in strict accordance with the procedures outlined in the manual The warranty does not include labor installation replacement parts or repairs delivery of replacement parts or repairs...

Page 4: ...Operation 23 Rotary Switch Positions 24 Resetting System Counters 25 Troubleshooting 26 Checking Individual Components 28 Checking Console Inputs 29 Plumbing Troubleshooting Chart 30 Plumbing Guidelin...

Page 5: ...pter Cable P N 14324 10 Flow Servo Pressure Run Hold Boom 6 Harness P N 14320 Console Mount Kit P N 13774 10 Boom Harness Booms 1 5 P N 17436 F Hardware Bag P N 13251 D Speed Sensor Mounting Bracket P...

Page 6: ...pumps Models available in 10 and 40 amp in both Std and PWM versions Includes modules and necessary cables P N 14692 FM500 P N 01500 50 FPT 5 5 GPM 500 PSI Max FM750 GFN P N 01501 75 FPT 2 40 GPM 150...

Page 7: ...7 System Layout S e c t i o n 1 5 c o n n e c t o r s SERVO VALVE...

Page 8: ...8 Wiring Diagram...

Page 9: ...alve Strainer Pump Tank Shut off Valve Items not included with this system Throttle Valve Items not included with this system Inline The flow is controlled by the servo valve located inline between pu...

Page 10: ...he MT 3405F II has an ON OFF switch on the console to turn the power off when the system is not being used Your MT 3405F II is equipped with a non volatile elec tronic mem o ry which does not re quire...

Page 11: ...isregard the following section on magnetic speed sensors and install the Vansco or other radar as described in the instructions included with the unit You will need an adapter cable to connect to rada...

Page 12: ...DY COLOR MAIN HARNESS TIE COLOR Speed Green Yellow Flow Green Green Run Hold Black Gray The optional Run hold sensor also uses the same type of connector as the speed and flow sensors However the Run...

Page 13: ...g the flowmeter remains full of fluid To avoid erratic flow readings allow a minimum of 6 of straight tubing at the flowmeter input and output If installation constraints don t allow this keep bends a...

Page 14: ...l operation may result The return line should tee from the main line just after the throttling valve See Illustration 8 The throttling valve is used to limit the output set maximum output of the pump...

Page 15: ...rap crimp on a connector and connect this lead to the relief valve positive terminal Connect the other terminal on the relief valve to ground T Fitting Servo Valve Relief Solenoid Installation cont El...

Page 16: ...ual CAL This key is used to enter exit the calibration mode Key Functions PROGRAM KEYS Used to increment and decrement the different calibration values RESET when not in CAL clears the selected counte...

Page 17: ...ra tion and Metric mode is selected Exit CAL by pressing and holding the CAL key until CAL disappears from the display ap prox i mate ly 1 second NOTE You must exit CAL to lock in Metric units ENGLISH...

Page 18: ...s being used for the en tire boom on the sprayer DO NOT enter the actual flow of your spray application FOR EXAMPLE If the min i mum flow rate for the nozzle you are using is 22 GPM at their minimum r...

Page 19: ...English units the SPEED CAL number is displayed in inches in metric it is displayed in centimeters SPEED CAL DISTANCE INLINE BYPASS The display will show InLinE or bYPASS Use the or buttons to toggle...

Page 20: ...ulator that is used in performing pre field checks When a typical operating speed is entered the MT 3405F II will respond as if you were actually driving that speed It allows you to simulate your spra...

Page 21: ...Tank Off or 1 65 535 Off Tank Low Set Point Sets Alarm Set Point if using TANK Function Off or 1 65 535 Off Auto Shut off Runs Servo Toward Minimum when in Hold On Off Off Auto Delay Time Delay Servo...

Page 22: ...ing the valve response speed If using a relatively fast valve 1 3 seconds open to close the system may become unstable with higher valve response speed numbers entered TEST SPEED SPEED FILL TANK SIZE...

Page 23: ...ate GPM or LPM can be monitored Automatic Operation When the Automatic mode is selected the console will control the servo valve to maintain the desired application rate GPS LPH when the vehicle speed...

Page 24: ...HOLD power is cycled or CALIBRATE is entered The Emergency Stop feature helps protect against chemical spills or over application if the Flow signal is lost TANK ALARM If a TANK SET POINT tank low nu...

Page 25: ...econd CLEAr will disappear and be replaced by 0 indicating that the selected pair of counters has been cleared Clearing Counters When the desired counter number is displayed press the RESET button and...

Page 26: ...in Cal mode and no booms are turned on Make sure system is in run and a boom switch is turned on also check Run Hold switch or sensor and connections Rotary switch in any position FILL will flash if...

Page 27: ...ck to see that a FLOW CAL number has been entered Also check cable for breaks or incomplete connection If the flowmeter is new or has not been used for a long period of time the turbine may be sticky...

Page 28: ...t should result in a very high resistance infinite MAGNETIC HALL EFFECT SPEED AND FLOW SENSORS Caution Improper connection or voltage could damage the Hall effect sensor The Hall effect sen sor works...

Page 29: ...position and turn at least one boom switch to ON Using a voltmeter or simple test light check from a good frame ground to each of the servo wires on the main harness connector You should get 0 volts o...

Page 30: ...Don t use longer hoses than necessary Avoid bends whenever possible Use as few fittings as possible Use full port valves or the next larger size valve Long hoses should be supported to avoid sagging a...

Page 31: ...ake sure pressure does not go too high Put the MT 3405F II in MAN and turn boom on Hold adjust switch to for about 30 seconds to fully close servo valve Turn booms OFF Now slowly screw handle in until...

Page 32: ...minimum flow output to booms NOTE must increase and decrease output If opposite check Inline Bypass setting on page 26 CAN T GET THERE If you can t get to the desired ap pli ca tion rate you may need...

Page 33: ...gher than the desired application rate Now is a good time to confirm that GPA GPM MPH WIDTH and PSI all coincide with the nozzle man u fac tur er s charts PSI may be slightly higher than indicated by...

Page 34: ...34 Appendices...

Page 35: ...e Cable Tie Speed Sensor Tap thread for bolts or weld Hub Top View ATV Wheels Two mounting examples are illustrated 1 Using one cable tie ribbed side toward magnets secure two magnets to the wheel hub...

Page 36: ...ed by the Hall effect speed sen sor must alternate as the shaft is turned The magnets provided by Micro Trak are marked with a punched dashed line on the SOUTH pole side of the magnet Attach magnets o...

Page 37: ...n the marker on the vehicle passes the starting flag to activate the distance counting function The console display numbers will increase adding to the distance total as you drive Drive the pre measur...

Page 38: ...ith the known amount of water run If the two amounts are within one or two per cent no fine tuning is required If the two amounts are more than two or three percent dif fer ent con tin ue with the nex...

Page 39: ...ed On a flat surface place each housing half on end Set and spin the turbine in each half It should spin freely If it does not spin freely remove the turbine wipe the shaft and try again If is still d...

Page 40: ...C GND FUSE HOLDER AND TEMINALS INSTALLED BY USER 10 NH3 ADAPTER CABLE P N 14366 15 10 WIRE EXTENSION CABLE P N 13222 P N 13273 NORMALLY PRE INSTALLED ON NH3 PLUMBING PANEL SPEED ACCESS Appendix E NH3...

Page 41: ...verview of Typ i cal Installation for NH3 Hall effect Speed Sensor or radar or GPS Speed Sensor Local Access Speed Connection Radar Speed Connection Main Harness Hitch Connection NH3 Heat Exchanger MT...

Page 42: ...E D C B A 15 10 Pin M P Extension Cable P N 13222 The LiquifierTM Kit P N 01817 An NH3 system can be connected using the NH3 Main Harness P N 14366 shown below The 10 pin connector plugs into the sta...

Page 43: ...quifier kit Another option although not recommended is to use the existing manifold making certain the old metering valve is in the maximum open position to allow for minimal restriction of flow throu...

Page 44: ...to one of the x x tee fittings and route along the tool bar frame to the vapor outlet connections on the Liquifier Repeat for other half of tool bar Allow enough extra hose to avoid kinking at hinge...

Page 45: ...one second WIDTH CAL FLOW CAL MIN FLOW ADJUST RATE TARGET RATE SPEED CAL INLINE BYPASS TEST SPEED VOLUME MINUTE DISTANCE AREA HOUR VOLUME 1 2 3 RATE SPEED AREA 1 2 3 CAL AUTO MAN RESET ____ TANK ___...

Page 46: ...H3 on page 56 Appendix E cont MT 3405FTM II Calibration Factors for NH3 FLOW CAL This po si tion is used to cal i brate the flow me ter for ac cu rate liquid mea sure ment The flowmeter has been calib...

Page 47: ...nd stop at the ending flag 3 Place the Run Hold switch in RUN when the marker on the vehicle passes the starting flag to activate the distance counting function The console display numbers will increa...

Page 48: ...at least 1 000 pounds of NH3 has been applied One nurse tank is preferred The larger the volume of NH3 applied the more accurate the calibration will be Obtain an accurate scaled weight of the partial...

Page 49: ...fold pressure stops climbing but FLOW RATE continues to climb vapor bubbles are present In hilly or rough conditions the nurse tank dip tube will not remain submerged allowing extra vapor in the syste...

Page 50: ...A WHT 20 GA BLK 10 PINM P150TOWER 20 GA BRN 20 GA RED 20 GA ORG 20 GA YEL 20 GA GRN 20 GA BLU 20 GA VIO 20 GA GRY 20 GA WHT 20 GA BLK 20 GA BRN 20 GA RED 20 GA ORG 20 GA YEL 20 GA GRN 20 GA BLU 20 GA...

Page 51: ...e Set turbine in non sensor housing Properly position gasket on housing Gasket may be reused a few times but will eventually need to be replaced Pipe thread compound is not absolutely necessary but wi...

Page 52: ...348 Appendix E cont MT 3405FTM II NH3 Specific Flowmeter Assembly FM 1500 N After assembly shaking flowmeter end to end should produce a rattling sound shaft end play Blowing into the meter from eithe...

Page 53: ...gurations Some basic 2 3 4 wire configurations are shown below If you need assistance for wiring other than shown contact Micro Trak for wiring instructions For 2 wire voltage reversing valves use P N...

Page 54: ...d VRA Testing Procedures CABLE CONNECTION Use a standard pin for pin not null modem serial communications cable to connect the Micro Trak console to the GPS Mapping controller One end of the cable sho...

Page 55: ...nd 3 Signal 4 Enable 3 4 2 1 4 3 1 2 P N14810 Signal Ground Common B A DICKEY johnRadarFordConnector DICKEY johnRadarDeutschConnector DICKEY johnRadarCannonConnector DICKEY johnRadarAmpConnector In Ca...

Page 56: ...Minute of Oil Flow Calculate the maximum gallons per minute GPM of oil flow required for your application There are 231 cubic inches of hydraulic oil per gallon so simply divide the maximum oil flow...

Page 57: ...e normal operating range of the nozzles However there may be instances where extra flow is needed greater than the output capacity of the nozzles on the primary boom in which case a secondary boom lin...

Page 58: ...dary Boom Control Primary Section Valves Secondary Section Valves SBE Signal Boom 1 Signal 2 3 4 5 Secondary Boom Enable The following shows a sample illustration of a wiring configuration NOTE Relief...

Page 59: ...ers 3 28 feet meters 1 09 yards kilometers 62 miles LAND MEASUREMENT square millimeters 0 00155 square inches square meters 10 764 square feet square meters 1 195 square yards hectares 2 47 acres squa...

Page 60: ...FM500 Flowmeter 14286 FM270 Flowmeter 14829 FM10 100 Flowmeter 14366 NH3 System Adapter Cable 14318 Power and Boom Console Harness Boom 120 Power Harness 240 14320 Flow Servo Run Hold and Relief Harne...

Page 61: ...61 NOTES...

Page 62: ...rak Systems Inc P N 14946 021819 M A N U F A C T U R E D I N U S A B Y 111 E LeRay Avenue P O Box 99 Eagle Lake MN 56024 0099 Toll Free 800 328 9613 507 257 3600 Fax 507 257 3001 www micro trak com tr...

Reviews: