8.7. Network inputs to MCS-MAGNUM
The MCS-Magnum can receive changes from the network to enable or disable the Network Run/Stop, Network Target
Reset (adjustments to the Cooling Target, Setpoint #1, based on Setpoint #21), Network Demand FLA, and Network
Demand Steps.
The MCS-Magnum must be set up to accept these inputs. The configuration file must contain a Network Run/Stop,
Network Target, Network Demand FLA, and Network Demand Steps sensors.
Magnum
BACnet ID
BACnet Name
Modbus
N2
Network Run/Stop
AV:246
Net_R/S
40201
BO:247
Network Target/Reset
AV:247
Net_Tar/Res
40202
AO:248
Network Demand/FLA
AV:248
Net_Demad_FLA
40204
AO:249
Network Demand/Steps
AV:249
Net_Demad_Steps
40205
AO:250
Note the following Information panel has a Network Run/Stop, and /or Network Target Reset sensors inputs indicated.
This is an example of how MCS-Config must be setup in the General Information and Evaporator Information panels.
The sensors must be set up as follows (This is only an example)