68
Chapter - 9. ALARMS- UNIT/COMPRESSOR / MODBUS
9.1. Unit Alarms
Modbus Info
BACnet Object Identifier
V17 Frimware
Unit Alarms
Function Type Register
BACnet Object
Type
Address
Relay
output
Modbus
BACnet
EMERGENCY_STOP
04:input Register
31011
AV: Ananlog Value
1296
HVAC//RTU HVAC//RTU
HVAC//RTU
FREEZE_PROTECTION
04:input Register
31012
AV: Ananlog Value
1297
HVAC//RTU HVAC//RTU
HVAC//RTU
HIGH_SUMP_TEMP
04:input Register
31013
AV: Ananlog Value
1298
HVAC//RTU HVAC//RTU
HVAC//RTU
PHASE_LOSS
04:input Register
31014
AV: Ananlog Value
1299
HVAC//RTU HVAC//RTU
HVAC//RTU
HIGH_DELTA_TEMP
04:input Register
31015
AV: Ananlog Value
1300
HVAC/
HVAC/
HVAC/
VOLTAGE
04:input Register
31016
AV: Ananlog Value
1301
HVAC//RTU HVAC//RTU
HVAC//RTU
SMOKE_ALARM
04:input Register
31017
AV: Ananlog Value
1302
No Support No Support No Support
FIRE_ALARM
04:input Register
31018
AV: Ananlog Value
1303
HVAC//RTU HVAC//RTU
HVAC//RTU
COMMON_CONDENSER
04:input Register
31019
AV: Ananlog Value
1304
HVAC//RTU HVAC//RTU
HVAC//RTU
CIRCUIT_CONDENSER
04:input Register
31020
AV: Ananlog Value
1305
HVAC//RTU HVAC//RTU
HVAC//RTU
Fuild Cooler Fan Fault
04:input Register
31021
AV: Ananlog Value
1306
HVAC//RTU HVAC//RTU
HVAC//RTU
PUMP_FAILURE
04:input Register
31022
AV: Ananlog Value
1307
HVAC//RTU HVAC//RTU
HVAC//RTU
PROCESS_PUMP_FAILURE
04:input Register
31023
AV: Ananlog Value
1308
HVAC//RTU HVAC//RTU
HVAC//RTU
PROCESS_PUMP_LOW_FLOW
04:input Register
31024
AV: Ananlog Value
1309
HVAC
HVAC
HVAC
BOILER_PUMP_FAULT
04:input Register
31025
AV: Ananlog Value
1310
HVAC
HVAC
HVAC
BOILER_PUMP_HIGH_AMPS
04:input Register
31026
AV: Ananlog Value
1311
HVAC
HVAC
HVAC
BOILER_PUMP_LOW_AMPS
04:input Register
31027
AV: Ananlog Value
1312
HVAC
HVAC
HVAC
BOILER_STAGE_FAULT
04:input Register
31028
AV: Ananlog Value
1313
HVAC
HVAC
HVAC
HIGH_WATER_TEMP
04:input Register
31029
AV: Ananlog Value
1314
HVAC//RTU HVAC//RTU
HVAC//RTU
OVERHEAT_PROTECTION
04:input Register
31030
AV: Ananlog Value
1315
HVAC
HVAC
HVAC
RTU_SUPPLY_DUCT
04:input Register
31031
AV: Ananlog Value
1316
RTU
RTU
RTU
RTU_EXHAUST_FAN_FAULT
04:input Register
31032
AV: Ananlog Value
1317
RTU
RTU
RTU
RTU_MOD_GAS_HEATER_FAULT
04:input Register
31033
AV: Ananlog Value
1318
RTU
RTU
RTU
RTU_SCR_HEATER_FAULT
04:input Register
31034
AV: Ananlog Value
1319
RTU
RTU
RTU
RTU_CLOGGED_FILTER
04:input Register
31035
AV: Ananlog Value
1320
RTU
RTU
RTU
RTU_HIGH_STATIC_PRESSURE
04:input Register
31036
AV: Ananlog Value
1321
RTU
RTU
RTU
RTU_LOW_STATIC_PRESSURE
04:input Register
31037
AV: Ananlog Value
1322
RTU
RTU
RTU
BOILER_PUMP_FLOW_FAULT
04:input Register
31038
AV: Ananlog Value
1323
HVAC
HVAC
HVAC
Leaving Water Temp. Sensor Fault 04:input Register
31039
AV: Ananlog Value
1324
HVAC//RTU HVAC//RTU
HVAC//RTU
Reutrn Water Temp. Sensor Fault
04:input Register
31040
AV: Ananlog Value
1325
HVAC//RTU HVAC//RTU
HVAC//RTU
Evap Water Pressure In #1 Sensor Fault 04:input Register
31041
AV: Ananlog Value
1326
HVAC//RTU HVAC//RTU
HVAC//RTU
Evap Water Pressure Out #1 Sensor Fault 04:input Register
31042
AV: Ananlog Value
1327
HVAC//RTU HVAC//RTU
HVAC//RTU
Evap Water Pressure In #2 Sensor Fault 04:input Register
31043
AV: Ananlog Value
1328
HVAC//RTU HVAC//RTU
HVAC//RTU
Evap Water Pressure Out #2 Sensor Fault 04:input Register
31044
AV: Ananlog Value
1329
HVAC//RTU HVAC//RTU
HVAC//RTU
RTU Zone Temp. Sensor Fault
04:input Register
31045
AV: Ananlog Value
1330
HVAC//RTU HVAC//RTU
HVAC//RTU
RTU Ambient Temp. Sensor Fault
04:input Register
31046
AV: Ananlog Value
1331
HVAC//RTU HVAC//RTU
HVAC//RTU