background image

MCS Total

Solution

for all your

Control

Needs

Energy Efficient and 

RoHS Compliant

5580 Enterprise Pkwy.

Fort Myers, FL 33905

Office: 239-694-0089

Fax: 239-694-0031

www.mcscontrols.com

BMS COMMUNICATION

MCS-BMS-GATEWAY

For Interfacing MCS-MAGNUM to:
Building Automation Systems Protocols:

MCS, Modbus RTU, Modbus IP, Ethernet,

BACnet IP, BACnet MS/TP,  N2, *LonWorks

Manual supports the following:
MCS-BMS-GATEWAY - see Chapter 4 & 5 for installation 
MCS-BMS-GATEWAY-NL-see Chapter 4 & 5 for installation 
MCS-BMS-GATEWAY-N54-see Chapter 6 for installation

MCS-MAGNUM

 

Rev. 3.5 May 24, 2022

Ethernet

Building 

Management 

System

MCS-Touch

Internet 

Router

MCS-BMS-Gateway Models

RS485  

• 

MCS-BMS-GATEWAY

  with LonWorks

• 

MCS-BMS-GATEWAY-NL

  (NO LonWorks)

• 

MCS-BMS-GATEWAY-N54

  (NO LonWorks)

RS485  

OR

Summary of Contents for MCS-BMS-GATEWAY-N54-see

Page 1: ...ols MCS Modbus RTU Modbus IP Ethernet BACnet IP BACnet MS TP N2 LonWorks Manual supports the following MCS BMS GATEWAY see Chapter 4 5 for installation MCS BMS GATEWAY NL see Chapter 4 5 for installat...

Page 2: ...rovisions shall be provided to ensure that this information remains proprietary by your employees agents and other personnel that may have access to this document Copyright 2022 Date Author Descriptio...

Page 3: ...MCS BMS GATEWAY 17 4 3 BMS Network Settings 18 4 3 1 BACnet MS TP N2 and Modbus IP to RTU 18 Figure 5 Protocol Selection Switch Tables 18 4 3 2 BACnet MS TP Setting the MAC Address for BMS Network 18...

Page 4: ...ssor Control State Chart 67 Chapter 9 ALARMS UNIT COMPRESSOR MODBUS 68 9 1 Unit Alarms 68 9 2 Compressor Alarms 69 9 3 MODBUS Alarms 71 Chapter 10 CREATING CSV FILES USING MCS CONFIG 76 9 4 How to Cre...

Page 5: ...eing configured by Network Management Tools such as LonMaker For binding implicit mode a Net work Management Tool is necessary to create the bindings It is possible to place a MCS BMS GATEWAY into a N...

Page 6: ...LCD The following steps will display the BACnet IP Network address and the the TCP IP port Press the Menu key select Serv Tools and then press the Enter key Use arrow to BACnet Setting then press Ente...

Page 7: ...et Mask and Default Gateway Press the Menu key select Serv Tools and then press the Enter key Select Ethernet Network then press Enter Set DYNAMIC IP to NO Set the IP Address Set the Subnet Mask Set D...

Page 8: ...HNSON N2 MCS Network Protocol Support Magnum MicroMag BACnet MCS BACnet RouterR2 Modbus IP In Development MCS IP MCS Ethernet Modbus RTU MCS 485 BACnet MS IP MCS BMS Gateway Johnson N2 MCS BMS Gateway...

Page 9: ...9 2 4 MCS MAGNUM USING RS 485 Using the RS485 the MCS Magnum can be connected to the BMS Modbus RTU or MCS 485 RS485 MCS MAGNUM MCS MAGNUM MCS MAGNUM Building Management System...

Page 10: ...ring Multiple MCS Controllers Using the RS485 the network must be wired controller to controller Star configurations not allowed Up to 30 controllers can be wired togetherMCS MAGNUM USING ETHERNET 04...

Page 11: ...onnect Internet access through router which allows connection via MCS Connect from anywhere 2 6 EXAMPLE NETWORK 2 6 1 Standalone MCS Magnum MCS Touch BMS Johnson N2 or BACnet MS TP Internet Access Eth...

Page 12: ...12 2 6 2 MULTIPLE MCS MAGNUM ENCLOSURES Internet Access BMS BACnet IP or Modbus IP...

Page 13: ...13 2 7 MULTIPLE MCS MAGNUM BMS RS485 WIRING DIAGRAM 04 14 2022 C...

Page 14: ...evice is found or not CONNECTIVITY The light shows the level of connectivity for the device Green is full connectivity Yellow is limited connectivity Blue is limited IP connectivity And red is connect...

Page 15: ...emplate or it can be a specific template specified by the OEM customer Setup Select File Transfer to upload files to the FieldServer gateway including configuration files firmware upgrades and more Se...

Page 16: ...e Map Descriptors detail page Again tabs across the top of the page provide quick access to settings status info stats and error stats User Messages Allows access to error messages info messages and d...

Page 17: ...t Device ID Set MCS MAGNUM BacNet port to 47808 in MCS CONFIG For Windows XP Customer ProtoCarrier Startup Guide Page 23 of 38 6 LONWORKS FPC C35 COMMISSIONING PROTOCARRIER ON A LONWORKS NETWORK Commi...

Page 18: ...less of how many devices are connected to MCS BMS GATEWAY Set the BACnet MS TP MAC addresses of the MCS BMS GATEWAY to a value between 1 to 127 MAC Master Addresses this is so that the BMS Front End c...

Page 19: ...P switches When more than one device is connected to the MCS BMS GATEWAY the subsequent BACnet Device In stance values will be sequential from the first previous device For example Given that Device I...

Page 20: ...Off 110 On Off Off Off 300 Off On Off Off 600 On On Off Off 1200 Off Off On Off 2400 On Off On Off 4800 Off On On Off 9600 On On On Off 19200 Off Off Off On 20833 On Off Off On 28800 Off On Off On 38...

Page 21: ...21 Chapter 5 Interfacing MCS BMS GATEWAY to Devices 5 1 MCS BMS GATEWAY Connection Ports Figure 7 MCS BMS GATEWAY...

Page 22: ...22 5 2 Wiring diagram for connecting the MCS Magnum Wire to 12 volt power supply 04 14 2022 C BMS Communication Rev 04 14 2022...

Page 23: ...enable successful communications between the MCS BMS GATEWAY and the MCS MAGNUM The MCS MAGNUM BACNET DEVICE ID must be set to the address specified on the MCS BMS GATEWAY s label The MCS MAGNUM BACNE...

Page 24: ...he magnum for the change to take effect The MCS MAGNUM IP must be set to the address specified on the MCS BMS GATEWAY s label Example 192 168 18 101 Range of default settings 101 150 The MCS MAGNUM IP...

Page 25: ...485 Device Network An RS 485 network with more than one device needs to have biasing to ensure proper communi cation The biasing only needs to be done on one device The MCS BMS GATEWAY has 510 Ohm res...

Page 26: ...GATEWAYas show below in Figure 13 Ensure that the power supply used complies with the specifications provided in chapter 9 6 MCS BMS GATEWAY accepts either 9 30VDC or 12 24 VAC on pins 4 and 5 7 Frame...

Page 27: ...27 0 Start up Guide MCS BMS GATEWAY N54 Chapter 6 MCS BMS GATEWAY N54 START UP GUIDE...

Page 28: ...lation between serial Ethernet devices and networks NOTE For troubleshooting assistance refer to Section 9 or any of the troubleshooting appendices in the related driver supplements Check the MSA Safe...

Page 29: ...quipment Setup ProtoNode Start up Guide 7 2 Equipment Setup 2 1 Mounting The ProtoNode can be mounted using the DIN rail mounting bracket on the back of the unit Figure 1 DIN Rail Bracket Din Rail Bra...

Page 30: ...30 Equipment Setup ProtoNode Start up Guide 8 2 2 Physical Dimensions R1 Serial Port Power Port R2 Serial Port Figure 2 ProtoNode FPC N54 Dimensions...

Page 31: ...t of the logic The bias resistor is 510 ohms which is in line with the BACnet spec It should only be enabled at one point on the bus for example on the field port were there are very weak bias resisto...

Page 32: ...n Figure 4 Termination resistor is also used to reduce noise It pulls the two lines of an idle bus together However the resistor would override the effect of any bias resistors if connected NOTE The R...

Page 33: ...ollowing baud rates are supported on the R1 and R2 Ports 9600 19200 38400 57600 76800 115000 NOTE Not all baud rates listed are supported by all protocols Check the specific protocol driver manual for...

Page 34: ...be added to the power supply of the host system A safety margin of 25 is recommended Figure 6 Required Current Draw for the Gateway Apply power to the ProtoNode as shown below in Figure 7 Ensure that...

Page 35: ...ontrol Panel click Network and Internet and then click Network and Sharing Center Click Change adapter settings on the left side of the window Right click on Local Area Connection and select Propertie...

Page 36: ...ar as untrusted This will cause the following pop up windows to appear When the Web Server Security Unconfigured window appears read the text and choose whether to move forward with HTTPS or HTTP When...

Page 37: ...the Username default is admin and the Password found on the label of the FieldServer NOTE There is also a QR code in the top right corner of the FieldServer label that shows the default unique passwor...

Page 38: ...reen will appear that allows the user to select which mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Sec...

Page 39: ...reen will appear that allows the user to select which mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Sec...

Page 40: ...hrase fields will appear under the mode selection Copy and paste the Certificate and Private Key text into their respective fields If the Private Key is encrypted type in the associated Passphrase Cli...

Page 41: ...ge to the Network Settings page follow the below instructions Find the Navigation tree across the left side of the screen Click the orange arrow next to the ProtoNode CN number and title to expand the...

Page 42: ...or the FieldServer s internet and network connections Click the Add Rule button to add a new row and set a new Destination Network Netmask and Gateway IP Address as needed Set the Priority for each co...

Page 43: ...ult Gateway and Domain Name Server1 2 NOTE If the FieldServer is connected to a router the IP Gateway of the FieldServer should be set to the same IP Address of the router Click Save to record and act...

Page 44: ...relevant device registers in the Config csv file for the initial start up If not the product is shipped with a sample config csv that shows an example of the drivers ordered In the main menu of the F...

Page 45: ...Setup then File Transfer and finally Update Browse and select the csv file open then click Submit Once download is complete a message bar will appear confirming that the configuration was updated suc...

Page 46: ...he main menu of the FS GUI screen click Setup then File Transfer Click the config csv link under the Retrieve heading in the middle section of the screen o The file will automatically download to the...

Page 47: ...ted driver supplements and configuration manual MSA Safety also offers a technical support on the MSA Safety website which contains a significant number of resources and documentation that may be of a...

Page 48: ...nload the FieldServer Toolbox zip via the MSA Safety website Extract the executable file and complete the installation Connect a standard Cat 5 Ethernet cable between the user s PC and ProtoNode Doubl...

Page 49: ...Node into the web browser or use the FieldServer Toolbox to connect to the ProtoNode Click on Diagnostics and Debugging Button then click on view and then on connections If there are any errors showin...

Page 50: ...ate parity data bits stop bits Check Serial device address Verify wiring Verify device is connected to the same subnet as the ProtoNode No COMS on the Ethernet protocol To fix this check the following...

Page 51: ...nostics page via one of the following methods o Open the FieldServer FS GUI page and click on Diagnostics in the Navigation panel o Open the FieldServer Toolbox software and click the diagnose icon of...

Page 52: ...is is the power light and should always be steady green when the unit is powered RX The RX LED will flash when a message is received on the serial port on the 3 pin connector If the serial port is not...

Page 53: ...r Next Gen Recovery 9 7 Internet Browser Software Support The following web browsers are supported Chrome Rev 57 and higher Firefox Rev 35 and higher Microsoft Edge Rev 41 and higher Safari Rev 3 and...

Page 54: ...Off On Off Off Off On 17 Off Off Off On Off Off On Off 18 Off Off Off On Off Off On On 19 Off Off Off On Off On Off Off 20 Off Off Off On Off On Off On 21 Off Off Off On Off On On Off 22 Off Off Off O...

Page 55: ...On On On Off 62 Off Off On On On On On On 63 Off On Off Off Off Off Off Off 64 Off On Off Off Off Off Off On 65 Off On Off Off Off Off On Off 66 Off On Off Off Off Off On On 67 Off On Off Off Off On O...

Page 56: ...f On On Off On 109 Off On On Off On On On Off 110 Off On On Off On On On On 111 Off On On On Off Off Off Off 112 Off On On On Off Off Off On 113 Off On On On Off Off On Off 114 Off On On On Off Off On...

Page 57: ...Off Off On On Off On On 155 On Off Off On On On Off Off 156 On Off Off On On On Off On 157 On Off Off On On On On Off 158 On Off Off On On On On On 159 On Off On Off Off Off Off Off 160 On Off On Off...

Page 58: ...Off Off On Off Off On 201 On On Off Off On Off On Off 202 On On Off Off On Off On On 203 On On Off Off On On Off Off 204 On On Off Off On On Off On 205 On On Off Off On On On Off 206 On On Off Off On...

Page 59: ...37 On On On Off On On On Off 238 On On On Off On On On On 239 On On On On Off Off Off Off 240 On On On On Off Off Off On 241 On On On On Off Off On Off 242 On On On On Off Off On On 243 On On On On Of...

Page 60: ...37 Sensor 2 6 AI 38 Refer to Config 30038 AI 38 Sensor 2 7 AI 39 Refer to Config 30039 AI 39 Sensor 2 8 AI 40 Refer to Config 30040 AI 40 Magnum BACnet ID BACnet Name Modbus Register N2 Sensor 2 9 AI...

Page 61: ...Config 00038 BO 38 Relay 3 9 BO 39 Refer to Config 00039 BO 39 Relay 3 10 BO 40 Refer to Config 00040 BO 40 Magnum BACnet ID BACnet Name Modbus N2 Relay 4 1 BO 41 Refer to Config 00041 BO 41 Relay 4...

Page 62: ...er to Config 30214 AO 14 Analog Out 3 3 AO 15 Refer to Config 30215 AO 15 Analog Out 3 4 AO 16 Refer to Config 30216 AO 16 Analog Out 4 1 AO 17 Refer to Config 30217 AO 17 Analog Out 4 2 AO 18 Refer t...

Page 63: ...ints are read only Magnum BACnet ID BACnet Name Modbus N2 Wanted FLA AV 3 Wanted FLA 30318 ADF 4 Steps Wanted AV 4 Steps Wanted On 30315 ADF 5 Steps On AV 5 Steps On 30316 ADF 6 Step Delay AV 6 Step D...

Page 64: ...Sat Disch 30357 ADF 61 Compressor 8 Disch SH AV 61 C8_Disch SH 30358 ADF 62 Compressor 8 Suct SH AV 62 C8_Suct SH 30356 ADF 63 Compressor 8 Oil Pres Diff AV 70 C8_Oil Pres Diff 30382 ADF 71 Compresso...

Page 65: ...mpressor 16 Oil Pres Diff AV 531 C16_Oil Pres Diff 30663 ADF 532 Compressor 17 FLA AV 496 C17_FLA 30580 ADF 497 Compressor 17 Sat Suction AV 499 C17_Sat Suct 30616 ADF 500 Compressor 17 Sat Disch AV 5...

Page 66: ...etwork Demand FLA and Network Demand Steps sensors Magnum BACnet ID BACnet Name Modbus N2 Network Run Stop AV 246 Net_R S 40201 BO 247 Network Target Reset AV 247 Net_Tar Res 40202 AO 248 Network Dema...

Page 67: ...N 34 HI TEMP UNLOAD 35 HI TEMP HOLD 36 SCROLL STEP1 37 SCROLL STEP2 38 SCROLL STEP3 39 SCROLL STEP4 12 RESERVED 13 AMBIENT OFF 14 PROCESS HEAT OFF 15 UNIT IS UNLOADED 16 UNIT IS LOADED 17 OFF TMP ICE...

Page 68: ...input Register 31027 AV Ananlog Value 1312 HVAC HVAC HVAC BOILER_STAGE_FAULT 04 input Register 31028 AV Ananlog Value 1313 HVAC HVAC HVAC HIGH_WATER_TEMP 04 input Register 31029 AV Ananlog Value 1314...

Page 69: ...HVAC RTU HVAC RTU LUBE_OIL_TIME HVAC RTU HVAC RTU HVAC RTU REFRIGERATION_LEAK HVAC RTU HVAC RTU HVAC RTU LOW_REFRIGERATION_TEMP HVAC RTU HVAC RTU HVAC RTU TOO_MANY_PURGES HVAC RTU HVAC RTU HVAC RTU E...

Page 70: ...ure Sensor Fault HVAC RTU HVAC RTU HVAC RTU Oil Temperature Sensor Fault HVAC RTU HVAC RTU HVAC RTU Motor Temperature Sensor Fault HVAC RTU HVAC RTU HVAC RTU Evap Refrigerant Temperature Sensor Fault...

Page 71: ...083 32134 32185 LOW_DISCHARGE_PSI 04 input Register 31217 31268 31319 31370 31421 31472 31523 31574 31625 31676 31727 31778 31829 31880 31931 31982 32033 32084 32135 32186 LUBE_OIL_TEMP 04 input Regis...

Page 72: ...99 31650 31701 31752 31803 31854 31905 31956 32007 32058 32109 32160 32211 Discharge Pressure Sensor Fault 04 input Register 31243 31294 31345 31396 31447 31498 31549 31600 31651 31702 31753 31804 318...

Page 73: ...70 1921 1972 2023 2074 2125 2176 2227 2278 2329 2380 LOW_DISCHARGE_PSI Analog Value 1412 1463 1514 1565 1616 1667 1718 1769 1820 1871 1922 1973 2024 2075 2126 2177 2228 2279 2330 2381 LUBE_OIL_TEMP An...

Page 74: ...70 1921 1972 2023 2074 2125 2176 2227 2278 2329 2380 LOW_DISCHARGE_PSI Analog Value 1412 1463 1514 1565 1616 1667 1718 1769 1820 1871 1922 1973 2024 2075 2126 2177 2228 2279 2330 2381 LUBE_OIL_TEMP An...

Page 75: ...1539 1590 1641 1692 1743 1794 1845 1896 1947 1998 2049 2100 2151 2202 2253 2304 2355 2406 Discharge Pressure Sensor Fault Analog Value 1438 1489 1540 1591 1642 1693 1744 1795 1846 1897 1948 1999 2050...

Page 76: ...Click on Setup 3 Be sure to set IP Address Subnet Mask Default Gateway MCS IP Port and Bacnet Device ID then save config file DO NOT CHANGE BACNET DEVICE ID ONCE CSV FILES ARE CREATED 4 Click on BMS...

Page 77: ...es This would be the time to name the CSV files there is a 15 character maximum not including the file extension If you do not name the file it will default to the first 15 characters of the config na...

Page 78: ...78 Providing HVAC R Control Solutions Worldwide 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com...

Reviews: