background image

MCS-Bacnet-Router2 

REVISION 2

14

4.3.2 

Backup and Restore

A configuration backup of the MCS-BACNET-ROUTER2 device can be downloaded via the Web interface. 

Click the backup link as shown in Figure 7 to start the download. The LIP- ME201 device assembles a single 

file including all required files. A file requestor dialog allows specifying the location where the backup file shall 

be stored.

To restore the device settings, simply select a previously generated backup file in the 

Restore Configuration 

section of the page by clicking the button next to the 

Filename 

field. Then press the 

Restore 

button.

The backed up configuration data consists of:

•  Device settings (Passwords, IP settings, BDT, ACL, etc.),

4.3.3 

Port Configuration

This menu allows configuring the device’s communications ports. For each communication port, which is 

available on the device and shown on the label (e.g., Port 1, Port  2, Ethernet), a corresponding configuration 

tab is provided by the Web UI. An example is shown in Figure 8. Each port tab contains a selection of available 

communication  protocols. By selecting a checkbox or radio button the various protocols can be enabled or 

disabled on the communication port. Some ports allow exclusive protocol activation only, other ports (e.g., the 

Ethernet port) allow multiple protocols bound to that port.

LIP-ME201 User Manual 

18 

LOYTEC  

Version 4.8 

LOYTEC electronics GmbH 

 

 

Figure 7: Backup/Restore page. 

4.2.3  Port Configuration 

This menu allows configuring the device’s communications ports. For each communication 
port, which is available on the device and shown on the label (e.g., Port 1, Port 2, 
Ethernet), a corresponding configuration tab is provided by the Web UI. An example is 
shown in Figure 8. Each port tab contains a selection of available communication 
protocols. By selecting a checkbox or radio button the various protocols can be enabled or 
disabled on the communication port. Some ports allow exclusive protocol activation only, 
other ports (e.g., the Ethernet port) allow multiple protocols bound to that port. 

 

Figure 8: Port Configuration Page. 

When selecting a protocol on a communication port, the protocol’s communication 
parameters are displayed in a box on the right-hand side. To save the settings of the 
currently opened protocol, click the 

Save Settings

 button. Pressing 

Get Settings

 retrieves 

the current settings from the device. 

4.2.4  IP Configuration 

The TCP/IP configuration is done under the Ethernet port tab as shown in Figure 9. The 
mandatory IP settings, which are needed to operate the device, are marked with a red 
asterisk (IP address, netmask, gateway). The 

Enable DHCP

 checkbox switches between 

manual entry of the IP address, netmask, and gateway address, and automatic configuration 
from a DHCP server. 

LIP-ME201 User Manual 

18 

LOYTEC  

Version 4.8 

LOYTEC electronics GmbH 

 

 

Figure 7: Backup/Restore page. 

4.2.3  Port Configuration 

This menu allows configuring the device’s communications ports. For each communication 
port, which is available on the device and shown on the label (e.g., Port 1, Port 2, 
Ethernet), a corresponding configuration tab is provided by the Web UI. An example is 
shown in Figure 8. Each port tab contains a selection of available communication 
protocols. By selecting a checkbox or radio button the various protocols can be enabled or 
disabled on the communication port. Some ports allow exclusive protocol activation only, 
other ports (e.g., the Ethernet port) allow multiple protocols bound to that port. 

 

Figure 8: Port Configuration Page. 

When selecting a protocol on a communication port, the protocol’s communication 
parameters are displayed in a box on the right-hand side. To save the settings of the 
currently opened protocol, click the 

Save Settings

 button. Pressing 

Get Settings

 retrieves 

the current settings from the device. 

4.2.4  IP Configuration 

The TCP/IP configuration is done under the Ethernet port tab as shown in Figure 9. The 
mandatory IP settings, which are needed to operate the device, are marked with a red 
asterisk (IP address, netmask, gateway). The 

Enable DHCP

 checkbox switches between 

manual entry of the IP address, netmask, and gateway address, and automatic configuration 
from a DHCP server. 

Summary of Contents for MCS-BACNET-ROUTER 2

Page 1: ...tal Solution for all your Control Needs 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com MCS BACNET ROUTER 2 Installation Reference Guide Revision 2 11 30 2017 ...

Page 2: ...ent shall be published used reproduced transmitted or disclosed to others out side your organization without the prior expressed written consent of Micro Control Systems Inc This document and the information contained herein shall be treated as proprietary Reasonable provisions shall be provided to ensure that this information remains proprietary by your employees agents and other personnel that m...

Page 3: ... Mounting 8 3 4 LED signals 8 3 4 1 Power LED 8 3 4 2 Status LED 8 3 4 3 MSTP Activity LED 8 3 4 4 Ethernet Link LED 8 3 4 5 Ethernet Activity LED 8 3 4 6 BACnet IP LED 8 3 4 7 BBMD LED 9 3 5 Status Button 9 3 6 Wiring 10 Chapter 4 Web Interface 11 4 1 Device Information and Account Management 11 4 2 Login and Passwords 12 4 3 Device Configuration 13 4 3 1 System Configuration 13 4 3 2 Backup and ...

Page 4: ...T Broadcast Distribution Table B IP BACnet over IP this is a BACnet data link layer DHCP Dynamic Host Configuration Protocol DNS Domain Name System DST Daylight Saving Time FD Foreign Device FTP File Transfer Protocol GMT Greenwich Mean Time IP Internet Protocol MAC Media Access Control MS TP Master Slave Token Passing this is a BACnet data link layer NAT Network Address Translation NTP Network Ti...

Page 5: ...s a BACnet time master and a BACnet MS TP slave proxy The MCS BACNET ROUTER2 also provides additional features such as optional write protection of the BDT a BACnet IP access control list and a simple BBMD communications test to troubleshoot the network The MS TP port supports remote Wireshark packet capture for troubleshooting the MS TP channel 1 1 1 Scope This document covers MCS BACNET ROUTER2 ...

Page 6: ... as the password Click on BACnet Config and setup the BACnet Device Configuration Click on Port Config and setup the BACnet IP and BACnet MS TP port configuration If the MCS BACNET ROUTER2 should also act as a BBMD click on BACnet BDT and setup the Broadcast Distribution Table Reboot the MCS BACNET ROUTER2 to commit the changes 2 3 MS TP Protocol Analyzer The MCS BACNET ROUTER2 is equipped with a ...

Page 7: ... are encoded using Code 128 An additional label is also supplied with the MCS BACNET ROUTER2 for documentation purposes Version 4 8 LOYTEC electronics GmbH 3 Hardware Installation 3 1 Enclosure The LIP ME201 enclosure is 107 mm wide for DIN rail mounting following DIN 43 880 see Figure 1 4 5 6 Status Button and LED 105 off on 1 2 3 4 5 6 7 DIP Switch 60 55 Serial Number Order Number 85 Console Con...

Page 8: ...flects a state Flicker is for 25 ms when there is activity on the MS TP data link layer Behavior Description Comment GREEN permanently flicker off Multi Master token ok flicker when traffic Normal condition on a multi master MS TP network ORANGE flicker Sole master flicker when traffic Normal condition on a single master MS TP network RED permanent flicker GREEN Token lost state flicker when trans...

Page 9: ...ory defaults over the console user interface 1 1 DIP Switch Settings The DIP switch assignment for the MCS BACNET ROUTER2 is shown in Table 2 Please leave all switches at default state DIP Switch Function Factory Default 1 Must be OFF OFF 2 Must be OFF OFF 3 Must be ON ON 4 Must be OFF OFF 5 Must be OFF OFF 6 Must be OFF OFF 7 Must be OFF OFF Table 2 DIP Switch Settings for MCS BACNET ROUTER2 1 2 ...

Page 10: ...ics GmbH 16 17 Power Supply 12 35 VDC or 12 24 VAC 10 Do not connect terminal 17 to earth ground Table 3 LIP ME201 Terminals 3 8 Wiring If BACnet over MS TP is enabled the MS TP network segment must be properly terminated with an LT 04 network terminator connected at each of the two ends of the segment media Important When using 2 wire MS TP earth ground must be connected to both terminal 15 and 1...

Page 11: ...ual IP address 6 Then open your Web browser and type in the default IP address 192 168 1 254 7 The device information page should appear as shown in Figure 3 The device information page shows information about the MCS BACNET ROUTER2 and the current firmware version It also contains operational parameters such as free memory system temperature and supply voltage LIP ME201 User Manual 15 LOYTEC Figu...

Page 12: ...e information page shows information about the LIP ME201 and the current firmware version It also contains operational parameters such as free memory system temperature and supply voltage Click through the menus on the left hand side to become familiar with the different screens If you click on Config in the left menu you will be asked to enter the administrator password in order to make changes t...

Page 13: ...urce It is specified as the offset to GMT in hours and minutes e g Vienna Austria is 01 00 New York USA is 06 00 For setting the daylight saving time DST predefined choices are offered for Europe and USA Canada DST can be switched off completely by choosing none or set manually for other regions In that case start and end date of DST must be entered in the fields below The next section on the page...

Page 14: ...the label e g Port 1 Port 2 Ethernet a corresponding configuration tab is provided by the Web UI An example is shown in Figure 8 Each port tab contains a selection of available communication protocols By selecting a checkbox or radio button the various protocols can be enabled or disabled on the communication port Some ports allow exclusive protocol activation only other ports e g the Ethernet por...

Page 15: ...rd protocols that are bound to the Ethernet interface are FTP Telnet and HTTP Web server By deselecting the checkbox those protocols can be individually disabled The standard UDP TCP ports can be changed in the respective protocol settings An example for the FTP server is shown for FTP in Figure 10 The FTP server is used for instance to update the firmware see Section 7 1 Note that HTTP for the We...

Page 16: ...out values are entered in seconds allowing decimal notation e g 7 5 On the settings for BACnet IP refer to Section 4 2 6 For configuring the MS TP data link refer to Section 4 2 7 Note If this page displays the message Device communication is disabled via BACnet network the device has been externally disabled Reboot the device to activate communication again 4 2 6 BACnet IP Configuration The BACne...

Page 17: ...ACnet IP Configuration In the field BACnet IP mode the operation mode of the device is selected Device Default In this mode the device operates as a regular BACnet IP device on the local network without other advanced features Foreign Device FD In this mode the device registers at an existing BBMD in the BACnet IP network as a foreign device It is used if the device is located as a single BACnet I...

Page 18: ...e setting for MS TP max master Decreasing the default value 127 of MS TP max master may reduce latency on the MS TP bus It is strongly recommended to leave the MS TP max info frames and the MS TP max master configuration options at their default settings In any case the MS TP max master number must be high enough to include the highest MS TP node number of all masters on the channel Slave devices ...

Page 19: ...MCS Bacnet Router2 REVISION 2 19 ...

Page 20: ...Providing HVAC R Control Solutions Worldwide 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com ...

Reviews: