MCS-Bacnet-Router2
REVISION 2
16
4.3.5
BACnet Device Configuration
Figure 11 shows the BACnet device configuration page. This configuration page allows setting the
Device ID
,
which is the instance part of the Object_Identifier property of the BACnet Device object. The field
Device
name
holds the name of the BACnet device object (property Object_Name).
Important:
The device ID and device name must be unique within the BACnet internetwork.
Further, the description and location can be configured. These configuration items correspond to the properties
Description, and Location respectively of the BACnet Device object. For tuning BACnet application timing
parameters, set
APDU timeout
,
APDU segment timeout
, and
APDU retry count
. The timeout values are
entered in seconds allowing decimal notation, e.g. "7.5".
On the settings for BACnet/IP refer to Section 4.2.6. For configuring the MS/TP data link refer to.
Note:
If this page displays the message "Device communication is disabled via BACnet network!" the device has
been externally disabled. Reboot the device to activate communication again.
4.3.6
BACnet/IP Configuration
The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the device, select the
BACnet/IP check box on the Ethernet tab of the port configuration page.
The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as shown in Figure
12. The
Network Number
of the BACnet/IP port must be configured to operate the built-in router. If the
LIP-ME201 User Manual
20
LOYTEC
Version 4.8
LOYTEC electronics GmbH
Figure 10: FTP server configuration on the Ethernet port.
4.2.5 BACnet Device Configuration
Figure 11 shows the BACnet device configuration page. This configuration page allows
setting the
Device ID
, which is the instance part of the Object_Identifier property of the
BACnet Device object. The field
Device name
holds the name of the BACnet device
object (property Object_Name).
Important:
The device ID and device name must be unique within the BACnet internetwork.
Figure 11: BACnet Device Configuration.
Further, the description and location can be configured. These configuration items
correspond to the properties Description, and Location respectively of the BACnet Device
object. For tuning BACnet application timing parameters, set
APDU timeout
,
APDU
segment timeout
, and
APDU retry count
. The timeout values are entered in seconds
allowing decimal notation, e.g. "7.5".
On the settings for BACnet/IP refer to Section 4.2.6. For configuring the MS/TP data link
refer to Section 4.2.7.
Note:
If this page displays the message "Device communication is disabled via BACnet network!"
the device has been externally disabled. Reboot the device to activate communication
again.
4.2.6 BACnet/IP Configuration
The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the
device, select the BACnet/IP checkbox on the Ethernet tab of the port configuration page.
The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 12. The
Network Number
of the BACnet/IP port must be configured to
operate the built-in router. If the BACnet/IP network uses a non-default UDP port number
LIP-ME201 User Manual
20
LOYTEC
Version 4.8
LOYTEC electronics GmbH
Figure 10: FTP server configuration on the Ethernet port.
4.2.5 BACnet Device Configuration
Figure 11 shows the BACnet device configuration page. This configuration page allows
setting the
Device ID
, which is the instance part of the Object_Identifier property of the
BACnet Device object. The field
Device name
holds the name of the BACnet device
object (property Object_Name).
Important:
The device ID and device name must be unique within the BACnet internetwork.
Figure 11: BACnet Device Configuration.
Further, the description and location can be configured. These configuration items
correspond to the properties Description, and Location respectively of the BACnet Device
object. For tuning BACnet application timing parameters, set
APDU timeout
,
APDU
segment timeout
, and
APDU retry count
. The timeout values are entered in seconds
allowing decimal notation, e.g. "7.5".
On the settings for BACnet/IP refer to Section 4.2.6. For configuring the MS/TP data link
refer to Section 4.2.7.
Note:
If this page displays the message "Device communication is disabled via BACnet network!"
the device has been externally disabled. Reboot the device to activate communication
again.
4.2.6 BACnet/IP Configuration
The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the
device, select the BACnet/IP checkbox on the Ethernet tab of the port configuration page.
The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as
shown in Figure 12. The
Network Number
of the BACnet/IP port must be configured to
operate the built-in router. If the BACnet/IP network uses a non-default UDP port number