background image

 

4

20.

 

Voltage Insulation: dc 2500V; 1 minute; 

21.

 

Temperature Drift: 100 PPM; 

22.

 

Output Ripple: 10mV; 

23.

 

Mounting: DIN Rail 35mm Mounting; 

Communication Protocol 

Order  

Register 

Address 

Content Meaning 

 

Byte 

1 0 
2 1 

E Active 

Energy 

3 2 
4 3 

R Reactive 

Energy 

5 4 Psum 

Total 

Active 

Power 

Qsum 

Total Reactive Power 

Csum 

Total Power Factor 

8 7 Ssum 

Total 

Apparent 

Power 

9 8  Ua  A 

Phase 

Voltage 

10 9  Ub  B 

Phase 

Voltage 

11 10  Uc  C 

Phase 

Voltage 

12 11  Uca  CA 

Line 

Voltage 

13 12  Uab  AB 

Line 

Voltage 

14 13  Ubc  BC 

Line 

Voltage 

15 

14 

Ia 

A Phase Current 

16 

15 

Ib 

B Phase Current 

17 

16 

Ic 

C Phase Current 

18 17  Pa A 

Phase 

Active 

Power 

19 18  Pb B 

Phase 

Active 

Power 

20 19  Pc C 

Phase 

Active 

Power 

21 

20 

Qa 

A Phase Reactive Power 

22 

21 

Qb 

B Phase Reactive Power 

23 

22 

Qc 

C Phase Reactive Power 

24 

23 

Ca 

A Phase Power Factor 

25 

24 

Cb 

B Phase Power Factor   

26 

25 

Cc 

C Phase Power Factor   

27 

26 

Sa 

A Phase Apparent Power 

28 

27 

Sc 

B Phase Apparent Power 

29 

28 

Sc 

C Phase Apparent Power 

   

Note 1: Output parameters of WB9128-1 power transducer can be selected by the User. Its default settings of 

address is 1, baud rate is 9600 bps and 1 stop bit. If the user needs other settings of communication address, baud 

rate, system types, output parameters and output specifications, WB9128-1 can be configured by configuration 

software, please refer to 

  WB9128-1 upper computer user configuration manual 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mianyang Weibo Electronics Co.,Ltd 

www.wb-my.com 

4

Summary of Contents for WB9128-1

Page 1: ...Power Transducer RS 485 Interface 3 phase 3 wire 3 phase 4 wire www wb my com Tel 86 816 2971265 Fax 86 816 2281934 ISO9001 ISO14000 ISO18000 Certified Quality Warranty Any quality problem found in WB series products we offer One year free charge of repair the products and six months guaranteed free charge of change and return the products ...

Page 2: ...he event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request the necessary information Standard application 1 Accuracy Accurate degree is conformed to IEC688 1992 2 Safety 2 1 Overload capability Overload capability is conformed to IEC688 1992 2 2 Isolation voltage Can be endured testing voltage is confo...

Page 3: ...put 2 5V 2 5V 0 5V 1 5V 3V 2V DC Current 10mA 10mA 0 20mA 4 20mA 12mA 8mA 8 Output Parameters E R PQ C S Ua Ub Uc Uab Ubc Uac Ia Ib Ic Pa Pb Pc Qa Qb Qc Ca Cb CC Sa Sb Sc 9 Accuracy Grade Current voltage 0 2 reactive active power power factor 0 5 10 Response Time 200ms 11 Auxiliary Power Supply DC 12V DC 24V 12 Static Current 65mA 13 Operating Temperature 0 50 14 Communication Protocol Modbus RTU ...

Page 4: ...se Active Power 2 19 18 Pb B Phase Active Power 2 20 19 Pc C Phase Active Power 2 21 20 Qa A Phase Reactive Power 2 22 21 Qb B Phase Reactive Power 2 23 22 Qc C Phase Reactive Power 2 24 23 Ca A Phase Power Factor 2 25 24 Cb B Phase Power Factor 2 26 25 Cc C Phase Power Factor 2 27 26 Sa A Phase Apparent Power 2 28 27 Sc B Phase Apparent Power 2 29 28 Sc C Phase Apparent Power 2 Note 1 Output para...

Page 5: ...n 8 pin 7 pin 6 pin Analogue OUT2 RS485B OUT1 RS485A GND E Analogue RS485 Converter PC Series Port Power Supply Current direction 3 phase 4 wire Load Sensor Current Direction A C B A B C N 5 pin 3 pin 1pin 2 4 pin 11 Pin 10 Pin 9 Pin 8 Pin 7 Pin 6 Pin Analogue OUT2 RS485B OUT1 RS485A GND E Analogue RS485 Converter PC Series Port Power Supply Current Direction Current Direction Mianyang Weibo Elect...

Page 6: ...nt Rx Imax 0 0001 Unsigned Integer Ia Ib Ic Power Factor Rx 0 0001 Signed Integer COSφ COSφa COSφb COSφc Active Power Rx Umax Imax 0 0001 Signed Integer Pa Pb Pc Reactive Power Rx Umax Imax 0 0001 Signed Integer Qa Qb Qc Apparent Power Rx Umax Imax 0 0001 Unsigned Integer Sa Sb Sc Total Active Power Rx Umax Imax 3 0 0001 Signed Integer Psum Total Reactive Power Rx Umax Imax 3 0 0001 Signed Integer...

Page 7: ... Uab Ubc Uca Iz 4 16 Ux 4mA 20mA 0V 5V Ia Ic Uz 0 5 Ix 1V 5V Ia Ic Uz 1 4 Ix Ia 0mA 20mA Ia Ic Iz 0 20 Ix Ic 4mA 20mA Ia Ic Iz 4 16 Ix 3 Phase 4 wire Parameter Name Output Specifications Actual Output Value Calculation Formula Uz Rated Output Line Voltage V Iz Rated Output Current mA 0V 5V Psum Uz 0 5 Ux Ix 3 1V 5V Psum Uz 1 4 Ux Ix 3 2 5V 2 5V Psum Uz 2 5 2 5 Ux Ix 3 3V 2V Psum Uz 3 2 Ux Ix 3 Psu...

Page 8: ...0 20 Ix Ic 4mA 20mA Ia Ib Ic Iz 4 16 Ix 0V 5V Pa Pb Pc Uz 0 5 Ux Ix 1V 5V Pa Pb Pc Uz 1 4 Ux Ix 2 5V 2 5V Pa Pb Pc Uz 2 5 2 5 Ux Ix Pa 3V 2V Pa Pb Pc Uz 3 2 Ux Ix Pb 0mA 20mA Pa Pb Pc Iz 0 20 Ux Ix Pc 4mA 20mA Pa Pb Pc Iz 4 16 Ux Ix Pa Pb Pc Iz 10 10 Ux Ix 10mA 10mA Pa Pb Pc Iz 12 8 Ux Ix 12mA 8mA 0V 5V Qa Qb Qc Uz 0 5 Ux Ix 1V 5V Qa Qb Qc Uz 1 4 Ux Ix 2 5V 2 5V Qa Qb Qc Uz 2 5 2 5 Ux Ix Qa 3V 2V ...

Page 9: ...d interference please pay attention to the shield of input wire and the output signal wire should be as short as possible For product intensive installation the space between each product should not be smaller than 10mm 5 Only use identified terminals 6 There is no lightening strike prevention circuit design in this product For out door and hazardous environment using please add protective alterna...

Reviews: