20301938
6
B-Vent Specialty Gas Fireplaces
FIREPLACE & FRAMING DIMENSIONS
Figure 1 -
Fireplace & Framing Dimensions
23
56
”
6" B-Vent flue
4” O.A. Inlet
37
56M
”
7
56O
”
22
56M
”
36”
38”
38
56O
” Rough Opening
Width - Peninsula
39” Rough Opening
Width - See-thru
40
56M
”
7
56O
”
1"
1"
42
56O
”
42
6
”
22
56
”
24
56
”
19”
12
6M
”
1938
BVST dims
3
556QE
”
13
6QE
”
Gas Line
Access
Gas Line
Access
Rough
Opening
Height
Rough
Opening
Depth
FIREPLACE FRAMING
It is best to frame your fireplace after it is positioned and
the vent system installed. Use 2 x 4’s and frame to local
building codes.
To install the fireplace facing flush with the finished wall,
position the framework to accommodate the thickness of
the finished wall.
It is not necessary to install a hearth extension with this
fireplace system.
The junction box should be wired to the electrical system
at the time of installation of the fireplace. Wiring must be
performed by a qualified person in a manner to conform
with National Electrical Code ANSI/NFPA 70 and all ap-
plicable local codes.
Do not fill spaces around firebox with in-
sulation or other materials. This could
cause a fire.
W
ARNING
Always check and make sure power is OFF
before attempting to install or service any
electrical wiring or components.
CAUTION