MHS Boilers TUDOR NHRE 18 Instructions For Installation, Servicing & Operation Download Page 18

17

TUDOR NHRE

It is important to ensure that all pipework is flushed to avoid the damage that foreign particles could

do to control valves, this is particularly important where installation is unvented.

1)

Open all outlet taps.

2)

Turn on water supply and allow the water heater to fill.

3)

Close taps in turn after having purged the system of air.

4)

Check for water leaks around the appliance and in particular around any valves or controls. 
Check again when the appliance is hot.

5)

Check that no water is passing to waste through any relief valves.

6)

Test the operation of any temperature and pressure relief and expansion valves by lifting/turning
the manually operated test lever/cap and observing that water flows freely and safely to waste.

7)

Check that the discharge pipe is installed so that it falls continuously and that no taps, valves or 
other shut off devices are installed in the pipe.

8)

Turn on the power supply & the appliance on/off switch - ensure protech system green 
lamp illuminates.

9)

The burner system should be commissioned by a competent Gas Engineer see section 20.

10)

Demonstrate operation to the user including the purpose and operation of any temperature and 
pressure relief valve or expansion valve and what to do if these valves should self operate.

11)

Hand over this manual to the user for future reference and advise that periodic checks of the 
equipment are essential for safety.
Advise that any expansion vessel in an unvented application may need to be recharged 
periodically by the installer.

Unvented system controls periodic checks must include:

a)

Check and clean the line strainer.

b)

Check pressure in expansion vessel and top up as necessary. Must be set 3.5 bar. Check should 
be carried out with expansion vessel drained of water to avoid that you cross-read system water
pressure.

c)

Check manually by lifting the test lever on the temperature and pressure relief valve.

d)

Check manually by turning the test knob on the expansion relief valve.

e)

Check discharge pipes from both relief valves to ensure no obstructions.

18.8 filling the water heater/

commissioning the water system

Summary of Contents for TUDOR NHRE 18

Page 1: ...TUDOR NHRE L 147 TUDOR NHRE RANGE OF DIRECT GAS FIRED WATER HEATERS INSTRUCTIONS FOR INSTALLATION SERVICING OPERATION FOR MODELS NHRE 18 26 36 60 90...

Page 2: ...d or Boosted Feed Systems 12 13 18 4 Unvented Installation Component Check List 14 15 18 5 Unvented Systems Terminating Safety Discharge Pipes 16 18 6 Secondary Circulation 18 7 Anti Stratification Sy...

Page 3: ...fence to install an unvented hot water storage system without notifying the Local Authority 3 0 building regulations Tudor NHRE Water Heaters are approved in accordance with EN89 and are CE marked C E...

Page 4: ...a powered active anode system which ensures best possible protection from waterside corrossion in all water supply areas and avoids the need for anode inspection replacement ease of maintenance Each...

Page 5: ...rimary aeration control Low energy standing pilot with piezo spark ignition flame failure protection Thermoelectric system with safety interlocking to over temperature limit thermostat and flue draugh...

Page 6: ...pliance see section 11 and sufficient persons must be employed if being manually handled to avoid injury to persons and damage to the product during moving and handling operations It is advised that t...

Page 7: ...72 432 781 G 3 4 F Draw Off Cold Feed Cold Feed Models 18 60 Hot Drawoff Models 18 60 Control Panel Inspection Cleaning Port Information Label E D C A G 290 B Drain 3 4 Recirc 1 F 275 Model 18 156 Mod...

Page 8: ...6 641 26 85 7 171 446 2 20 0 37 0 5 NHRE 60 350 67 57 7 08 5 20 535 1460 1110 512 1327 977 22 85 7 247 597 2 20 0 37 0 5 NHRE 90 285 99 84 2 10 47 7 68 558 1925 1640 525 1728 1443 12 85 7 270 555 1 20...

Page 9: ...chemicals produce vapours which can cause rapid failure of thermocouples burners and the water heater tank walls if they are drawn into the combustion air supply Therefore if this water heater will b...

Page 10: ...he diameter of the flue used must not be smaller than the flue connection on the appliance draught divertor and must be installed in accordance with the requirements of BS 5440 Part 1 BS 6644 or Briti...

Page 11: ...n valve must be installed as low as possible and must not be positioned above the level of the drain tapping on the appliance The drain tapping is positioned at the lowest point of the vessel and is c...

Page 12: ...fig 3 To install a Tudor NHRE Water Heater as an unvented hot water storage package then a Water Byelaws scheme approved kit of safety devices valves and fittings complying with BS7206 1990 and satisf...

Page 13: ...nc Non Return Valve Remove and Discard Plug Connect Expansion Vessel To This Port Pressure Limiting Valve Set 3 5 bar Inc Strainer Plugged Tapping For The Take Off of A Balanced Pressure Cold Supply i...

Page 14: ...FI BSP Check valve core assembly with integral G1 balanced cold G3 4 vessel G3 4 expansion relief valve connections CORE 255 001 3 3 4 MI BSP Inlet 22mm relief connection expansion relief valve set 6...

Page 15: ...t sizes Worked Example The example below is G 3 4 Temperature and Pressure Relief valve with a discharge pipe D2 having 4 no elbows and length of 7m from the Tundish to the point of discharge From Tab...

Page 16: ...ard discharges at low level ie up to 100mm above external surfaces such as car parks hard standings grassed areas etc are acceptable providing that where children may play and otherwise come into cont...

Page 17: ...perature Pressure Relief Valve Isolation Valve Small Bronze Pump HW Draw offs fig 8 If the installation is unvented then the following information regarding system water capacity is of the utmost impo...

Page 18: ...re protech system green lamp illuminates 9 The burner system should be commissioned by a competent Gas Engineer see section 20 10 Demonstrate operation to the user including the purpose and operation...

Page 19: ...injectors ignition button stop button piezoelectric ignitor burner pressure tapping restrictor location detail restrictor gas valve outlet port NHRE 18 gas regulation block detail outlet restrictor bu...

Page 20: ...jectors Nat Gas group H G20 34 02 MJ m3 20 Propane G31 46 34 MJ m3 37 Current Designation Reference Net calorific value 15 C 1013 mbar Nominal Supply Pressure mbar Equipment Type NHRE Pilot Flame Inje...

Page 21: ...h button 1 for 20 seconds Light the pilot flame using the piezoelectric ignition 2 by keeping the button 1 pressed right down Repeat the operation until the pilot flame lights If the pilot flame goes...

Page 22: ...e operation until the pilot flame lights Allow the thermocouple to heat by keeping the control button 1 pressed right down Release the button after 30 seconds The pilot flame must remain alight should...

Page 23: ...electricity supply If there is a risk of freezing then the appliance should be isolated from the water supply and then completely drained Important Note If the power supply is to be turned off for mor...

Page 24: ...ed out at intervals not exceeding 12 months Electrically isolate the appliance Isolate the gas supply to the appliance Disconnect the gas supply and the electrical connection to the multifunctional ga...

Page 25: ...ight Pilot flame extinguishes Burner does not light Hot water temperature too low Smell of burnt gas Possible causes Symptoms 25 0 trip of flue spillage detection safety device In the event that the f...

Page 26: ...RE 27 0 exploded diagram 26 0 guarantee The Tudor NHRE range of gas fired water heaters carry the following guarantee against defects in material or manufacturing process Tank 3 Years All other compon...

Page 27: ...26 TUDOR NHRE 28 0 parts list...

Page 28: ...ifications are not binding in detail All offers and sales are subject to the Company s current terms and conditions of sale 35 Nobel Square Burnt Mills Industrial Estate Basildon Essex SS13 1LT Tel 01...

Reviews: