29
STRATA1
3 8 & 3 8 / 4 6 C O M B I
LSV
SV
IV
Strainer
DOC
DOC
NRV
DOC
Calorifier/Indirect
Hotwater Cylinder
DOC
DOC
CWM
AAV
Strata 1-38Boiler
Expansion
Vessel
HWS Primary
Pump 2 A Max.
Filling Point
Condense Waste
Vertical Low Velocity
Mixing Header
Max Velocity
0.5 m/s
Heating Pump
2 A Max.
Heating Load
OS
C
S T
IV
IV
IV
IV
PS
Strainer
NRV
IV
OS =
Outside air temperature sensor.
Used where direct-on-boiler
weather compensated flow
temperatures are required.
C =
Room controls, either RE2132
modulating room unit from MHS
Boilers or a room thermostat.
S/T =
Hot water temperature controls,
either “S”, an HWS sensor from
MHS Boilers or “T”, a cylinder
thermostat.
PS =
Low water pressure cut off switch.
System pumps to be no greater
than 2 amps
system type 5
Typical Single Strata 1 boiler installation serving heating & domestic hot water (not
Combi) with hot water priority. Hot water & heating circuits both have index resistance
exceeding boiler pump residual head* & are served by independent pumps from a
low velocity mixing header. Heating flow temperature may be fixed/constant or
weather variable.
* See page 24
17.0 hydraulic system design (contd)