![MHS Boilers Alpha Jetstream MD Installation And User Manual Download Page 4](http://html1.mh-extra.com/html/mhs-boilers/alpha-jetstream-md/alpha-jetstream-md_installation-and-user-manual_1783514004.webp)
TECHNICAL INFORMATION
Boiler type
MD 4
MD 5
MD 6
MD 7
MD 8
MD 9
Number of sections
4 5 6 7 8 9
Product-ID number– Notified body number
86/AT/572 – CE0086
Rated heat output
kW
105 144 184 223 262 300
Flue gas resistance
mmwg
wg
4 9 16 20 23 33
Combustion
diameter
mm
370
chamber depth
mm
450 580 715 845 975 1105
Length L
mm
744 878 1012 1146 1280 1414
Burner mounting
diameter
mm
170
dimensions depth
mm
115
Return/flow connections
DN
65 (2 ½ “BSP M)
Flue gas temperature
o
C
185
Flue connection diameter
mm
208
Weight (boiler block)
kg
430 510 590 670 750 830
Weight (water content)
kg
49 61 73 85 96 108
Flow temperature control
o
C
30
–
90
Natural
gas* m
3
/h
11.98 16.5 21.04 25.57 29.97 34.36
Fuel LPG**
m
3
/h
8.83 12.16 15.5 18.83 22.07 25.31
Consump. 35 sec oil***
kg/h
9.7 13.35 17 20.7 24.24 27.8
Heat input
to boiler
Natural gas, LPG,
35 secoil
kW
115 158 202 245 288 329