Installation-Operation-Maintenance
GZ 2 - GZ 4 / 100 - 1450 kW
18
Connections
Burner
type
Motor voltage
Motor
output
Connected wattage
GZ 2
230 V WS 50 Hz 0,25 kW 0,37 kW, ca. 2 A
GZ 3.0 230 V WS 50 Hz 0,45 kW 0,7 kW, ca. 3,2 A
GZ 3.1
400 V DS 50 Hz
1,1 kW 1,4 kW, ca. 3 A
GZ 3.2
400 V DS 50 Hz
1,1 kW 1,4 kW, ca. 3 A
GZ 3.3
400 V DS 50 Hz
1,1 kW 1,4 kW, ca. 3 A
GZ 4
400 V DS 50 Hz
3,0 kW 3,3 kW, ca. 6 A
Boiler connections
Electric supply diagram
Assembly with silencer hood for GZ 3
and GZ 4
When a silencer hood is fitted, the pipe double nipple may have
to be lengthened to a size of 200 mm.
The pipe length between gas ramps and burner
should be as short possible. For gas burners GZ 3 and
GZ 4, the max. pipe length is 800 mm. A bracket is required
to take the weight of the gas ramps.
The dimension H must be checked before erecting boilers with-
out boiler foundations.
Fig. 18: Assembly with silencer hood for GZ 3 and GZ 4
Type
D1
D2
M
GZ 2.1
130 160 ÷ 180 8/10
GZ 2.2
140 160 ÷ 180 8/10
GZ 3.0/1 150 180 ÷ 205 10
GZ 3.2/3 162 220 ÷ 240 10
GZ 4
195 246 ÷ 276 12