general characteristics of Galaxy PW™ UPS
UPS power rating in kVA
100
130
150
180
200
225
Normal AC input
number of conductors
3 phases
rated voltage and tolerances
480 V ± 10% (adjustable to ± 15%)
rated frequency and tolerances
60 Hz / ± 10%
THDI
< 14%
< 11%
< 10%
< 8%
< 7.6%
< 7.5%
power factor
up to 0,9
Bypass AC input
number of conductors
3 phases 3 neutral
rated voltage and tolerances
480 V / ± 10%
rated frequency and tolerances
60 Hz / ± 10%
Load
number of conductors
3 phases 3 neutral
Ph/Ph voltages
480 V
Ph/N voltages
277 V
voltage fluctuations
± 1%
adjustable frequency and tolerances
(on battery power)
60 Hz ± 0,05 Hz
synchronization with bypass
± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz)
voltage variation for 0 to 100% load step change
± 2% (with battery)
permissible overloads
150% for 1 minute, 125% for 10 minutes
Isc Ph/Ph (% of I rated)
4.7
3.6
3.2
2.6
2.4
2.1
Isc Ph/N (% of I rated)
7.4
5.7
5
4.1
3.7
3.3
THDU Ph/Ph and Ph/N for linear load
< 1,5% Ph/Ph, < 2% Ph/N
THDU Ph/Ph and Ph/N for non-linear load
< 2% Ph/Ph, < 3% Ph/N
(at 80% of Pn)
Battery
standard battery type
gas-recombination sealed lead-acid battery
UPS characteristics
active power (kW)
100
130
150
180
200
225
efficiency at 50% load (%)
90.5
91
92
92.5
92.5
93
(values ± 1%)
efficiency at 100% load (%)
92.5
93
93
93
93.5
93.5
(values ± 1%)
heat losses (1)
in KW
8.1
9.8
11.3
13.5
13.9
14.1
in cal./s
1940
2350
2700
3240
3340
3380
storage temperature range
-25 °C to +70 °C
operating temperature range
0 °C to 35 °C (40 °C for 8 hours)
relative humidity
95% maximum
maximum operating altitude without derating
< 1000 meters
noise level (dBA)
62
63
64
65
67
68
dimensions (mm)
width
1215
depth
840
height
1900 ± 10
weight (lbs/kg)
3050/1388
standards
design
NFPA / NEC / NEMA / OSMA
product and safety
UL 1778 - ULC
electromagnetic compatibility
FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41
(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.
User’s Manual
Summary of Contents for Galaxy PW
Page 1: ...Galaxy PW 100 to 225 kVA User s Manual w w w m g e u p s c o m ...
Page 2: ......
Page 4: ...ii Chapter name Galaxy PW 100 to 225 kVA User s Manual This page intentionally left blank ...
Page 6: ...This page intentionally left blank iv ...
Page 8: ...This page intentionally left blank vi ...
Page 40: ...This page intentionally left blank 32 ...
Page 42: ...34 ...
Page 43: ...35 ...
Page 44: ...1660 Scenic Avenue Costa Mesa California 92626 714 557 1636 w w w m g e u p s c o m ...