4—5
Although six button states are detectable, not every button combination has an assigned task. button
states/combinations that have no assigned task will simply be ignored.
The “Utility Power Present” does NOT reflect the state of the UPS output. If, for example,
the UPS has shut down due to an output overload, the Utility Power Present LED may be
solidly ON but the UPS output could be turned off (due to the overload).
4F. Fault Alarms
LED Status
Audible Alarm Pattern
UPS Action
Fault "
" LED flashes until
Low Run time Warning
Warning when there is less than
alarm is acknowledged or
(short-long-short beep)
3 minutes of back-up time
cleared.
remaining.
Fault "
" LED flashes until
Low Battery Warning/Shutdown Occurs within 1 minute of UPS
alarm is acknowledged or
(short-long-long beep)
shutdown. Could also indicate
cleared.
a faulty battery charger.
Fault "
" LED flashes until
High Battery Warning
There is a problem with the
alarm is acknowledged or
(short-short-short-long beep)
battery system.
problem is corrected.
Fault "
" LED and Charge
Charger Problem Warning
The battery system may not be
"
" LED flashes until alarm
(long-short-long-short beep)
plugged into an AC source or
is acknowledged or problem
there is a charger problem.
is corrected.
Fault "
" LED Battery Fail
Battery/Inverter Test Failure
Indicates failed battery/inverter
"
" LED flashes until alarm
(long-short-short-short beep)
test performed every 28 days.
is acknowledged or cleared.
Clear fault and recharge battery
for 8 hours. Manually initiate test
again. If fault recurs, call for
service.
Fault "
" LED flashes until
Output Voltage Low
Output shuts down to protect
alarm is acknowledged or
(on inverter,
load from low voltage.
cleared.
short-long-short-short beep)
Fault "
" LED flashes until
Output Voltage High
Output shuts down to protect
alarm is acknowledged or
(on inverter,
load from high voltage.
cleared.
short-short-short-short beep)
Fault "
" LED and Overload
Output Overload
Flashes when load exceeds
"
" LED flashes until alarm
Warning/Shutdown
105%, solid when overload is
is acknowledged or problem
(long-long-long beep)
101-105%, automatically clears
corrected, flashes when
when load is reduced.
shutdown is imminent, and
solid if warning only.
!
!
!
!
!
!
!
!