Table 5a.
Esprit Models 3 and 4 Rack UPS Specifications (Continued)
Item
Specification
Comment
Design standards
Safety; UL, cUL 1778, Emissions;
FCC A, Surge protection; ANSI
C62.41, Transportation; (drop test),
IEC 68 level 1, (vibration), IEC
68.2-6 level 3, testing; PowerCet
tested
Input connection
NEMA 5-30/50 w/ six foot cord
Output connections
1 NEMA 5 30/50 and 4 5-15
Auxiliary DC input
1 each special female connector on
Provides additional battery time
UPS (18" cord and male connector
on optional battery)
Size
1 each (UPS, battery)
5.25" X 7.25" X 19"
Weight
65/70 lbs.. total
MTBF 200K
hours
Sizing Guide and Battery Runtimes
(In minutes, 0.62 PF)
Unix Server
1
2
3
4
server
servers
servers
servers
PC Server
1
2
3
4
5
6
7
8
server
servers
servers
servers
servers
servers
servers
servers
VA
500
1000
1500
2000
2500
3000
3500
4000
Esprit 3 SLR
90
40
28
19
11
6
Esprit 3 SLR
+ 1 Ext. Batt.
240
90
40
28
19
15
Esprit 3 SLR
+ 2 Ext. Batt.
360
150
90
60
45
38
Esprit 4 SLR
120
50
30
20
15
12
9
7
Esprit 4 SLR
+ 1 Ext. Batt.
240
100
72
45
35
28
24
18
Esprit 4 SLR
+ 2 Ext. Batt.
360
180
110
75
55
45
35
29
Extended Battery Runtime
(internal plus extended battery, in minutes, 0.7 PF)
Extended Batteries (Qty.)
1
2
3
4
Model
Esprit 3
12
30
45
60
Esprit 4
15
25
38
49
Note: All battery times above are typical.