3
Installation
page 7
ELC X-Series-V1.3-09.16-GB
subject to technical alterations
3.2.2 Overview profile of the cable gasket X4-X8
The IP protection level given in chapter 6 is only guaranteed if every cable’s lead-in is
completely sealed. It is therefore necessary to use cables of the nominal diameters given in
the table below.
Cable gasket
Cable
diameter
Connector
designation
Function
Connector
no. of pins
Connector
type eta
ID.:
Cable
length
(gasket to
connector)
Plug contact
7.5mm ±5%
X3
Bus out
(T-coupler)
3
9546
120mm
blank wire or
ferrule
9.3mm ± 5%
X600 (1, 3)
Lamp output
3
9532
155mm
blank wire or
ferrule
4.9mm ± 5%
X600 (2)
PE
5.2mm ± 5%
X806
Control
7
9535
130mm
ferrule
7.5mm ± 5%
X1
Bus in
4
9545
120mm
blank wire or
ferrule
6.7mm ± 5%
X805
Control
11
9536
130mm
ferrule
7.5mm ± 5%
X2
Bus out
4
9545
120mm
blank wire or
ferrule
12.2mm ± 5%
X100
Mains input
(2 x Phase,
2 x PE)
4
9531
490mm
blank wire or
ferrule
If the control concept requires fewer control and bus cables the
holes of the rubber surround have to be sealed with blank plugs
(available as accessories).
☞