5. Monitoring, warning, error, repair
page 31
ELC PE22B-PE35B V1.0-05.19-GB
Subject to technical alterations
Bit 5
:
If the ELC cannot ignite the lamp the
{Lamp Ignition Failed}
bit will be set and
remains in this status as long as
{Start Lamp}=1
in
[Lamp Control]
. The
{Lamp
Ignition Failed}
bit is reset as soon as
{Start Lamp}
in
[Lamp Control]
is reset.
Bit 7
:
The
{Init Signal Ok}
bit reflects the status of the
Init-Pin X1.1
of the
initialisation signal (see paragraph 3.4.2).
{Init Signal Ok}=1
means 24 V on X1.1, the lamp may be ignited and operated
normally.
{Init Signal Ok}=0
means 0 V on X1.1, the lamp cannot be operated.
To render the ELC operational again in case
{Init Signal Ok}=0
the
initialisation signal on X1.1 has to be 24V
and
the start signal {Start Lamp} has
to be reset.
Bit 2
,
Bit 3 und
Bit 6
:
{n/a}
bits (not available) are reserved for future applications.