FP4, FP4W
45
IP address:
[value]
[1]
ModbusTCP port:
[value]
[2]
Mask:
[value]
[1]
Gate:
[value]
[1]
[1]: These parameters should correspond to the network where the device is intended to
operate.
[2]: It is recommended to use the 502 port dedicated to Modbus TCP, port 80 is not
allowed (reserved for the device’s web server).
11.3.2
RS-485 port
Recorder RS-485 port settings must correspond to the master device settings.
Baud Rate: 115200
(1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200)
[1]
Parity: EVEN
(NONE, EVEN, ODD)
[2]
ModbusRTU Address: 1
(1, 2, .., 247)
[3]
[1]: Baud Rate should be set to the highest possible value. For high distances or high
interference level, data transmission speed may need to be decreased. Low
transmission speed extends the reading time.
[2]: Parity control of each bite.
[3]: In RS-485 standard, up to 32 transmitters/receivers can be connected to the data
transmission line. Each slave-type device must have a different address assigned.
For more information on Modbus registers addresses and data format refer to section
MODBUS RTU / MODBUS TCP TRANSMISSION PROTOCOL
.
11.4 Channels settings
The channel number is selected using the drop-down list, located in the upper left
corner of the screen. The description of the channel can be edited by clicking on the text in
the
Tag
field. Then, the screen keyboard will pop up.
The channels are permanently assigned to the inputs. Channels 1 and 2 correspond to
analogue inputs IN1 and IN2, channels 3 and 4 correspond to analogue inputs IN3 and
IN4, channels 5 and 6 are math channels (computing the formula entered by the user).
Depending on the channel selection, different settings are available.
Switching between settings windows is possible by using tabs:
Inputs
,
General
,
Σ1
,
Σ2
,
Alarm 1
and
Alarm 2
. Confirm
and cancel
buttons are common for all
sub-windows, clicking on these buttons results in toggles to the Main Menu.
!
Settings of the individual channels may be copied and pasted to another
measurement channel. Detailed information is given in section
Copying
channel settings
.