![Metronic FP4 Operating Manual Download Page 33](http://html.mh-extra.com/html/metronic/fp4/fp4_operating-manual_1779919033.webp)
FP4, FP4W
33
Maximum power consumption
for 100 .. 240 VAC 50/60 Hz power supply:
8 W (typically 6 W)
for 24 VDC (20 .. 30 VDC) power supply:
6 W (typically 4 W)
Security
The internal delay fuse 3.15 A, the exchange only
by the service company
Electrical connections (FP4)
Type
screw terminal connectors
Wire cross section
solid and flexible 0.14 .. 1.5 mm
2
flexible with bootlace ferrule 0.25 .. 1.5 mm
2
AWG 30 / 14
Electrical connections (FP4W)
Type
spring type terminal block
Wire cross section
supply 230 VAC: 0.2 .. 2.5 mm
2
others: 0.2 .. 1.5 mm
2
Cable glands
supply: one M16 cable gland, cable diameter:
5 .. 10 mm
I/O signals: three M20 cable glands, cable
diameter: 8 .. 13 mm
Ethernet: one M20 cable gland, cable diameter:
6 mm (the possibility of installing a cable with
an RJ-45 connector)
Mechanical Dimensions
– enclosure (FP4)
Enclosure type
panel mount, nonflammable plastic material
‘Noryl’
Dimensions with connectors (w X h X d)
144 mm X 72 mm X 127 mm
Dimensions of panel cut-out (w X h)
138
+1
mm X 68
+0.7
mm
Maximum panel thickness
5 mm
Weight
0.5 kg
Protection class
IP30 on front panel side
IP30 on rear panel side
Mechanical Dimensions
– enclosure (FP4W)
Enclosure type
Wall mount, polycarbonate material
Dimensions (w X h X d)
without cable glands:
213 mm x 185 mm x 102 mm
with cable glands:
213 mm x 215 mm x 102 mm
Weight
c.a. 0.8 kg
Protection class
IP54
Environmental conditions (FP4, FP4W)
Ambient temperature
FP4:
0 .. +50 °C
FP4W: -2
0 .. +50 °C
Relative humidity
5 .. 95%
(without steam condensation)
Maximum altitude
<2000 m above sea level
Storage temperature
-30 ..
+70 °C
Degree of pollution
PD2
EMC
EMC Directive 2014/30/EU
EN 61326-1:2013 Table 2 (immunity)
EN 61326-1:2013 Class A (emission)
RoHS
RoHS Directive 2011/65/EU
Installation location
FP4: Indoor only
FP4W: Indoor or outdoor
(2)
(2)
If additional protection against atmospheric precipitation is provided (roofing), the device can be installed
outdoor
.