FP4, FP4W
44
11.2.1 Outputs
Relay outputs (RL1 .. RL4)
Mode: Disabled
(Disabled, Normally open, Normally closed, Pulsation)
[1]
[1]: In the
Normally open
mode the relay circuit is closed when an event is reported (e.g.
exceeded alarm-control threshold). In the
Normally closed
mode, the relay circuit is
normally closed when idle, and is opened when an event is reported.
Pulsation
-
when an event is reported, the relay circuit is closed and opened at approx. 1Hz
frequency
(e.g. a light indicator blinks - alarm notification). After the acknowledge, the
relay output remains active if the threshold is still exceeded (the indicator is lit). If the
exceeding returns to normal
– the relay output will be inactive. In the
Disabled
mode,
the selected relay output is open.
Note: SSR relays remain open in the event of power failure.
Analog output
Source: Channel 3
(Disabled, Channel 1, .., 6)
[1]
[1]: Selection the output mode as switched off or as a retransmission of the selected
channel value in the form of 4-20mA current loop.
4-20 mA span may be set as a sub-range of retransmitted channel span by entering
the process values for 4 mA and 20 mA respectively.
Failure value: Disabled
(Disabled, Constant)
[3]
[2]: Setting the failure value.
11.3 Communication settings
The window has been divided into two sub-windows: for Ethernet and RS-485
communication settings. Switching between settings windows is possible by using tabs.
Confirm
and cancel
buttons are common for both sub-windows, clicking on
these buttons results in toggles to the Main Menu.
Fig. 11.3 A
n example view of the ‘Communication’ settings window.
11.3.1 Ethernet port
To ensure proper communication between the device and the master system, all
communication parameters need to be configured.