FP4, FP4W
17
5.2 Wiring transducers to analogue inputs
The device has two analogue inputs, which can work in one of the selected modes:
0/4-20mA (active/passive transducers), R/RTD type input, U type input. It should be taken
into account that the configuration of jumpers inside the device is necessary. Detailed
description is in section
Configuration of jumpers inside the device
.
0/4-20mA input type (passive transducers)
Fig. 5.5 Wiring passive transducers to 0/4-20mA input type.
Terminal No.
(FP4)
Description
Terminal No.
(FP4W)
1
(+)
4
(+)
+24V OUT (22 mA max) / I+
Transducer power supply. Each output is protected by
resetable polymer 50 mA fuse.
Current loop signal input (+)
21
(+)
24
(+)
2
(A)
5
(A)
I-
Current loop signal input (-)
22
(A)
25
(A)
3
(B)
6
(B)
Not used
23
(B)
26
(B)
0/4-20mA input type (active transducers)
Fig. 5.6 Wiring active transducers to 0/4-20mA input type.
Terminal No.
(FP4)
Description
Terminal No.
(FP4W)
1
(+)
4
(+)
Not used
21
(+)
24
(+)
2
(A)
5
(A)
I+
Current loop signal input (+)
22
(A)
25
(A)
3
(B)
6
(B)
I-
Current loop signal input (-)
23
(B)
26
(B)