A 1179, A 1257, A 1395 Flex current clamps 

 

4

 

1  Introducing the A1179/A1257/A1395 

 

The A1179/A1257 (A1179 has measuring ranges 20A/200A2000A, A1257 has 

measuring ranges 30A/300/3000A) Flexible Current Clamps consist of three flexible 
sensors and an electronic module. The A1395 has measuring ranges 30A/300/3000A 
and two flexible sensors and an electronic module.  

A current measurement can be carried out on the two/three phases 

simultaneously, with a suitable output voltage for the Measuring ANALYZER / 
Multimeter. The flexible sensor permits measurements on conductors where standard 
clamp-on current transformers can not be used. It is particularly useful for installation in 
tight spaces, or around breaker panels, cable bundles, wide or large bus bars and 
irregular shapes. Unlike standard current transformers, this flexible CP does not use 
magnetic cores. The transformation principle is based on an air core. It presents 
virtually no load to the system under test, has a low phase shift and excellent frequency 
response.  

The electronic module can detect if the measured current amplitude is too big for 

the selected range (crest factor of the amplifier is 3.0). This overrange detection is 
indicated by a blinking range LED diode for currently selected range. If the overrange 
current was detected but is not currently present, the user can reset the blinking Range 
LED by pressing the key. If the overrange is present also when the key is pressed, the 
range will be changed to the less sensitive range. The electronic module has low 
battery indication as well. 

Additionally, A1179/A1257/A1395 cannot be damaged by overloads. The 

A1179/A1257/A1395 Flexible Current Clamps are insensitive to DC current and 
measure only the AC component of the measured signal. 
 

2 Features 

  Direct connection to 1V AC input on measuring  device, and optional connection to 

other meters (data logger, multi-meters,etc.),on demand 

  Switch ON, switch OFF and two/three measuring ranges with one key selection 

(2000/3000 Arms, 200/300 Arms and 20/30 Arms) 

  Overrange indication for measurement circuitry (blinking LED at corresponding 

range) 

 mV 

output 

 Waterproof 

sensor 

  Minimum angle shift to accomplish accurate power measurements 

 High 

accuracy 

  Simultaneous measurement of the two/three phases 

  Total rejection of d.c.component 

  Friendly-use of the closing-opening system of the current sensor (even if wearing 

gloves) due to its highly ergonomic design 

  It is possible to set the seal on the closing system of the current clamp. 

  Very light, flexible and fully adaptable to busbar trunking system and insulated 

cables 

  Strengthened security, regardless the working environment:industrial or services 

  Possibility of external power supply at 220 V a.c./12 V d.c. 

  Build in charger (Low Bat LED on) 

  Low battery indication (blinking Low Bat LED) 

Summary of Contents for A 1179

Page 1: ...amps A 1179 A 1257 A 1395 User Manual Version 1 6 Code No 20 751 167 KOMETEC Karl Oelkers e K Mess und Pr fger te Shop Mozartstr 10 D 88097 Eriskirch T 07541 955 1313 F 07541 955 1131 info kometec de...

Page 2: ...www metrel si Mark on your equipment certifies that this equipment meets the requirements of the EC European Community regulations concerning safety and electromagnetic compatibility 2007 2008 2012 Me...

Page 3: ...A1257 A1395 Flexible Current Clamps 7 6 1 Battery and charging 7 6 1 1 New battery cells or cells unused for a longer period 7 6 2 User interface 8 6 2 1 A1179 A1257 A1395 states regarding power supp...

Page 4: ...ut is not currently present the user can reset the blinking Range LED by pressing the key If the overrange is present also when the key is pressed the range will be changed to the less sensitive range...

Page 5: ...insulation Also look for loose or weakened components Do not use a clamp that is cracked damaged or has a defective cable Never use the clamp on a circuit with voltages higher than 1000 V CAT III or...

Page 6: ...with the relevant European standards 5 Output connecting The A1179 A1257 A1395 Flexible Current Clamps can be used with any Metrel Power Analyzer Oscilloscope or Multimeter that has the following fea...

Page 7: ...ed to the clamps and power off the A1179 A1257 Insert cells correctly otherwise the A1179 A1257 A1395 will not operate and the battery could be discharged Remove all battery cells from the battery com...

Page 8: ...cause an improper charging and incorrect discharging during normal usage of the entire battery pack it results in heating of the battery pack significantly decreased operation time reversed polarity...

Page 9: ...A1395 module states regarding power supply and charging and actions to change between them are defined State How is it indicating What is happening POWER OFF All LED diodes OFF External power supply i...

Page 10: ...ge is too small for measured current amplitude peak value If the overrange current was detected but currently it is not present any more the user can reset blinking Range LED by pressing the key see T...

Page 11: ...verrange OVERRANGE DETECTION 2000 3000 A OVERRANGE DETECTION 2000 3000 A Press the key RANGE 2000 3000 A Table 6 5 Change state table when single overrange is detected State before Action to change st...

Page 12: ...pling See Picture 7 1 5 It is very important that the conductor is as the center and perpendicular to the measuring head if it is no possible additional error of 2 of full scale can occur 6 Do not mea...

Page 13: ...it Do not use liquids based on petrol or hydrocarbons Do not spill cleaning liquid over the A1179 A1257 A1395 9 Service For repairs under or out of warranty time please contact your Metrel distributor...

Page 14: ...l output voltage 1 V at full scale Minimum load impedance in output 2 10 k internal output is 150 Phase error 1 50Hz 10 1 5kHz Crest factor Up to 3 0 Overrange indication Corresponding range LED indic...

Page 15: ...nce conditions 4 Expression of error measurement in refence conditions error Iresidual I measured x 100 linearity Accuracy 5 Full charged NIMiH 2200 mAh at 25 C 6 Distance between cable and clamp coup...

Reviews: