UNT Controller—Unitary Controller (UNT) 91
Appendix B: UNT100/101
This section contains information specific to the discontinued
UNT100/101. To troubleshoot the UNT100/101, refer to the
Troubleshooting section of this technical bulletin.
The following list contains features of the UNT100/101 which differ from
the other UNT types.
•
No earth ground connections are allowed when wiring a
UNT100/101 series controller.
•
The N2 bus is not isolated. The secondary of the 24 VAC transformer
cannot be grounded.
•
The BIs can accept dry contacts only, not 24 VAC. They can also
accept 100 Hz as accumulator input.
•
The BO is not jumper selectable. The triac switches to the common
side of 24 VAC only.