UNT Controller—Unitary Controller (UNT) 47
1 2 3 4 5 6
BINARY IN
ANALOG INPUTS
BINARY OUTPUTS
70
BINARY INPUT
ANALOG INPUTS
1 2 3 4 5 6
1 2 3 4
ANALOG INPUTS
COMMON
T O
ZONE
STA T
BI NA RY OUTPUT
1 2 3 4 5 6 7 8
Z BUS
DSI
1 2 3 4 5 6
BINARY COM
1
2
3
6
5
4
Note: Since the UNT is a self-terminating device, end-of-line termination
for the N2 Bus is not required.
N2 REF
N2 -
N2 +
N2 +
N2 -
N2 REF
NCU (TB1 on
Communication
Terminal Board)
HRD
GRD
SFT
GRD
N2-
N2+
REF
SFT
GRD
REF N2- N2+
n2wire-a
Figure 24: Connecting the UNT Controller to an NCM
Table 14: Terminal Locations
TB1 Terminal Function
Number
UNT Connection
Chassis Ground
6
None
Soft Ground
5
None
N2 Ref
4
REF
Soft Ground
3
None
N2B -
2
N2 Bus: N2-
N2B +
1
N2 Bus: N2+
N2 Wiring to the
Network Control
Module