6 Conventional Products—6424 Projected Beam Type Smoke Detector
Table 3: Specification Summary
General
Range
30 to 330 ft
Sensitivity
30% ±5% Total Obscuration or
55% ±5% Total Obscuration
Response Time
Alarm
15 Seconds Maximum
Trouble
15 Seconds Maximum
Trouble Condition
95% or More Obscuration
Improper Initial Alignment
Self-compensation limit reached
(service needed)
Test/Reset Features
Obscuration Filters (ALARM/NO ALARM)
Local Alarm Reset Switch
Remote Test and Reset Switch Capability
(compatible with RTS451 Test Station
with Magnet)
Indicators
Alarm
Remote Output
Local LED (red)
Trouble
Remote Output
Local LED (yellow)
Normal Operation
Local LED (flashing green)
Alignment Aid
LED Bar Graph (four red LEDs)
Relays
Alarm
Trouble
Environmental
Temperature
–30 to 55°C (–22 to 131°F)
Humidity
95% RH, Non-condensing
Mechanical
Weight
Receiver
1.5 lb (663 g)
Transmitter
1.3 lb (598 g)
Mounting
Ceiling or Wall,
Separate Mounting Brackets Provided
Wiring
Plug with Attached Cable
Adjustment Angle
Ceiling
±30° Horizontal/60° Vertical
Wall
±90° Horizontal/60° Vertical
Electrical (Receiver)
Voltage
20 to 32 VDC
Maximum Ripple Voltage
30% of Nominal (Peak-to-Peak)
Current (24 VDC)
Standby
10 mA Maximum
Alarm
28.4 mA Maximum
Continued on next page . . .