35
8. TECHNICAL DATA
FLUX 1
FLUX 2
Measured flow range
Nl/min
0 to 2000
0 to 4000
Fluid
Compressed air free of any lubricants and inert gases
Fluid temperature
°C
0 to 50
Direction of flow
Unidirectional
Measuring method
Thermal
Working pressure range
bar
0 to 10
MPa
0 to 1
psi
0 to 145
Pressure drop
None
Temperature range
°C
0 to 50
Threaded ports
1/2"
1"
Degree of protection
IP65
Weight
g
585
705
IO-Link supply voltage range
VDC
15 - 27 (with IO-Link Master)
Current consumption
mA
80 mA (at 24VDC)
DISPLAY
lnstant flow rate
Nl/min
0 to 2200
0 to 4400
Cumulative flow rate
Nl
999.999.999
Nm
3
999.999
Nft
3
35.320.000
Pressure
n
bar
0 to 10
Resolution
bar
0.01
PRECISION
●
Flow rate
Measuring range
0 to 100% of the full scale
Single unit display accuracy
from 0 to 20% of the FS - better than ±1% of the FS
from 20% to 100% of the FS - better than ±3% of the FS
Display accuracy of unit installed in an SY unit
from 0 to 20% of the FS - better than ±2% of the FS
from 20% to 100% of the FS - better than ±6% of the FS
Repeatability
±1% of the FS
Temperature characteristic
Version with pressure transducer
Automatic compensation of fluid temperature from 0 to 50°
Between 0 and 15°C and between 35 and 50°C ±0.6% of the FS every °C
Version without pressure transducer
Without compensation, between 0 and 15°C and between 35 and 50°C
±1.2 % of the FS every °C
Pressure
Measuring range
bar
0 to 10
Display accuracy
±2% of the FS
DIGITAL OUTPUT
Operating mode, if set on flow rate
Level switch, Band switch, Value switch, Cyclic pulse
Min. accumulated volume by pulse (pulse width 100 msec)
10
20
1
1
Response mode, with pressure mode setting
Level switch, Band switch
Hysteresis
Adjustable
n
In versions with pressure transducer.
●
At a pressure of 5 bar and a fluid temperature of 25°C ±10°C.