24
3. MENU ACCESS (ONLY FOR MODELS WITH DISPLAY)
Parameter setting
Press the SET UP buttons
simultaneously for
1 second
to access the parameter settings.
Use the vertical arrow keys
to select the function.
Press the right arrow key
to access the function parameters.
Use the vertical arrow keys
to change the parameter.
Press the right arrow
to confirm.
Press the left arrow
to return to the previous menu.
3.1 SYSTEM
The compressed air system is connected through the threaded holes on the body.
In order to prevent impurities or excessive condensation from causing malfunctions, it is recommended to supply the FLUX with
dry 20μm-filtered compressed air at a pressure not exceeding 10 bar.
3.1.1 SYN filter
Set to ON when the FLUX is installed after a Syntesi unit filter to optimise flow rate reading.
3.1.2 Gas type
Helps optimise the measurement of the current flow and consumption figures.
Types of gas: Air
Helium
CO
2
Nitrogen
3.1.3 K ENERGY
K-Energy is the amount of Wh consumed to generate 1 Nm
3
of compressed air, depending on the efficiency of the
production system.
Used to calculate the current power (kW) and accumulated energy (kWh) consumption.
3.2 I/O
3.2.1 Digital Output – available for models with display
The digital output can be set as a “Normally Open” or “Normally Closed” contact.
It can relate to current flow, pressure or air consumption.
3.2.1.1 Parameters
• Contact type: NO/NC
• Reference:
-
FLOW
:
the output switches according to flow values.
Threshold Setting:
function – LEVEL SWITCH, BAND SWITCH;
OUT SET/HI – Flow value for output activation;
OUT RST/LO – Flow value for output de-activation.
-
PRESSURE
:
the output switches according to pressure values.
Threshold Setting:
function – LEVEL SWITCH, BAND SWITCH;
OUT SET/HI – Pressure value for output activation;
OUT RST/LO – Pressure value for output de-activation.
-
VOLUME CONSUMPTION
: Function – CONTACT SWITCH, the output switches at the value set under CNT Target;
Function – CYCLIC PULSE, the output switches for 100 ms each time the value set in CNT
Target is reached. The minimum flow rate can be set to 10 Nl for FLUX 1 and 20 Nl
for FLUX 2.