Stop temperature.

 

Central heating installation 
activation 

If the top buffer temperature drops below this value, in order to save 
electrical  power,  the  mixer  pumps  and  HUW  pumps  will  be 
deactivated.  This  function  is  particularly  useful  when  working  in 
GRATE mode. 

15.5

 

 MIXER 

 

Mixer 1-4 settings 

Mixer suport

 

  Off 

The mixer actuator and pump are not in operation. 

  CH On 

It  is  being  used  when  a mixing  circuit is loading  a  heat  installation  of 
CH. The maximum mixing circuit temperature is not being limited, the 
mixer  is  fully  opened  during  alarms  e.g.  with  boiler  overheating. 
Attention:  do  not  use  this  option  when  the  heat  installation  is  made 
with  pipes  not  resistant  for  high  temperatures.  In  such  cases  it  is 
recommended to set the mixer operation for FLOOR switched on. 

  Floor On 

It  is  being  used  when  the  mixer  circuit  is  loading  floor  heating 
installation.  The  maximum  mixer  circuit  temperature  is  limited  to  the 

value of max. mixer set temperature. 
Attention:  after  choosing  the  option 

–  FLOOR  switched  on  the 

parameter of max. mixer set temperature should be so edited, that the 
floor  heating  will  be  not  damaged  and  there  would  be  no  danger  of 
scalding.  

  Pump Only 

By  the  moment  when  the  mixer  circuit  temperature  exceeds  the  set 
temperature in the parameter mixer set temperature,  the mixer pump 
supply  will  be  shut  down.  When  the  circuit  temperature  will  drop  by 
2˚C then the pump will again be switched on. This option is usually be 
used for control of floor heating pump in situation, when this pump is 
operating together with thermostatic valve without actuator.  

Thermostat select* 

Options to choose from: 
Shut  down:  (it  cuts  the  influence  of  room  thermostat  upon  the  boiler 
operation.) 
Universal:  (it  turns  on  the  no/nc  room  thermostat  coupled  to  42-43 
contacts, it is required to use thermostats with 1K hysteresis.) 
ecoSTER:  (this  option  is  available  after  remote  control  device 
ecoSTER TOUCH is being connected, thermostat signal is being send 
from room panel.) 

Minimum mixer temperature 

It is the parameter used for limitation of choosing too low value of set 
mixer  circuit  temperature  by  the  user.  Automatic  regulation  (e.g. 
periodic  temperature  reduction)  also  does  not  cause  the  reduction  of 
set temperature value below the value given in this parameter. 

Maximum mixer temperature 

This parameter has two functions: 
_  it  enables  the  limitation  of  choosing  too  high  value  of  set  mixer 
temperature  by  the  user.  Automatic  regulation  (correction  upon 
heating  curve,  that  comes  from  outside  temperature)  also  does  not 
cause  crossing  the  set  temperature  above  the  value  given  for  this 
parameter.  
_ when the

 

Mixer Support = On

then the mixer pump will shut down 

by  max.  mixer  temperature  +5˚C,  which  protects  the  floor  against 
destruction. For the floor heating it should be set for the value below 
45+/-

50 ˚C or even lower, when the thermal resistance of this floor is 

lower. Attention: setting too lower value of this parameter can lead to 
unnecessary shut down of the pump.

  

 

Valve opening time 

The time of valve full opening should be entered 

– this time can be 

read from the nameplate of valve actuator, e.g. 140s. 

Proportionality range 

This parameter affects the movement of the mixer actuator. Increasing 
this  value  results  in  the  mixer  reaching  the  set  temperature  faster. 
Setting this parameter to excessive values causes deregulation of the 

Summary of Contents for ecoMAX860P2-T

Page 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Page 2: ...2...

Page 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Page 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Page 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Page 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Page 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Page 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Page 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Page 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Page 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Page 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Page 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Page 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Page 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Page 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Page 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Page 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Page 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Page 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Page 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Page 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Page 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Page 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Page 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Page 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Page 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Page 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Page 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Page 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Page 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Page 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Page 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Page 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Page 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Page 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Page 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Page 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Page 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Page 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Page 43: ......

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Reviews: