Metal-Fach ecoMAX860P2-T Installation And Operating Manual Download Page 15

15 

 

 

In  the  given  example,  the  regulator  will  set 
the  decrease  of  preset  temperature  by  3  °C 
from  00:00  to  06:00,  and  will  keep  the 
preset  value  (without  the  decrease)  from 
06:00 to 09:00. Then, it will set the decrease 
by  5  °C  from  09:00  to  15:00,  and  will  keep 
the  preset  value  (without  the  decrease) 
again  from  15:00  to  22:00;  and  again  will 
set  the  decrease  by  3  °C  from  22:00  to 
23:59. 

 

Time  interval  is  disregarded  when 
its  decrease  is  set  to  "0"  even 
though  "from...  to  ..."  values  have 
been entered. 

 

Decrease 

of 

preset 

boiler 

temperature 

in 

selected 

time 

intervals is indicated by the symbol: 

 on the main screen 

 

8.17

 

 Fuel level setup 

 
Activating the fuel level gauge 

In  order  to  enable  display  of  the  fuel  level, 
set value of parameter 

Boiler settings 

Fuel level 

 Alarm level

 

to  a  value  greater  than  zero,  e.g.  10%.  By 
pressing  the  right  or  left  box  in  the  main 
window  you  can  select  the  fuel  level 
indicator. Fuel level can also be displayed on 
the ecoSTER TOUCH room panel. 
 
Operation of fuel level indicator 
Any  time  upon  filling  fuel  tank,  press  and 
hold  pressed  current  fuel  level  value. 
Following prompt appears: 

 

"Set  fuel  level  at  100%  Once  selected  and 
confirmed YES, fuel level is set at 100%. 
Once  selected  and  confirmed  YES,  fuel  level 
is set to 100%. 
Note:  Fuel  may  be  replenished  at  any  time 
without  a  need  to  wait  for  complete  empty 
fuel  tank.  Replenish  fuel  always  to  the  level 
corresponding to 100% level of the fuel tank 
and set 100% level as described above.  

 

Description of operation 
The regulator calculates the fuel level basing 
on  the  current  fuel  consumption.  Default 
settings  do  not  always  correspond  to  the 
actual  consumption  of  fuel  by  the  given 
boiler,  therefore,  for  proper  operation  this 
method  requires  the  regulator  user  to 
perform  level  calibration.  No  additional  fuel 
level sensors are required. 

 

Calibration  
To  perform  calibration  -  fill  the  fuel  tank  to 
the  level  corresponding  to  its  full  load  and 
set the parameter: 

Boiler settings 

 Fuel Level 

→ 

Fuel level 

calibration 

 Fuel Level 100% 

The indicator in the main window will be set 
to  100%.  On-going  calibration  process  is 
signalled  by  flashing  fuel  level  gauge.  The 
gauge will flash until the time of marking the 
point  corresponding  to  minimal  fuel  level. 
One 

must 

systematically 

control 

the 

decreasing level of fuel in the bin. When the 
level  reaches  the  requested  minimum,  set 
the value of the parameter: 

Boiler settings 

 Fuel Level 

→ 

Fuel level 

calibration 

 Fuel Level 0% 

Calibration  can  be  skipped  if  the

  Feeder 

Efficiency

 and 

Tank capacity

, parameters are 

set  correctly  in: 

Menu 

  Service  settings 

 Burner settings 

→ 

Operation.

 

Summary of Contents for ecoMAX860P2-T

Page 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Page 2: ...2...

Page 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Page 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Page 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Page 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Page 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Page 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Page 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Page 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Page 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Page 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Page 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Page 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Page 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Page 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Page 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Page 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Page 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Page 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Page 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Page 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Page 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Page 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Page 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Page 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Page 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Page 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Page 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Page 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Page 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Page 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Page 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Page 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Page 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Page 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Page 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Page 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Page 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Page 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Page 43: ......

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Reviews: