Metal-Fach ecoMAX860P2-T Installation And Operating Manual Download Page 17

17 

 

This  alarm  will  occur  after  the  feeder 
temperature exceeds the service parameter: 

Service  setting  s

→ 

Burner  settings 

→ 

Max. feeder temp. 

In  such  cases,  the  regulator  will  attempt  to 
push out the burning fuel from the feeder by 
switching  it  on  for  a  short  time.  If  three 
consecutive attempts to switch the feeder on 
do  not  reduce  the  temperature,  the  feeder 
will  be  switched  on  for  a  a  longer  time  and 
report  a  constant  alarm.  Before  returning  to 
regular  operation,  remove  the  excess  fuel 
from the combustion chamber. For additional 
information, see pt. 15. 

 

The 

flame 

return 

protection 

function will not work if there is no 
power supply to the regulator. 

 

 

 

The  regulator  cannot  be  used  as 
the  only  flame  return  protection. 
Use 

additional 

automatic 

protection. 

 

9.3

 

Feeder control system failure 

The  regulator  has  an  additional  protection 
preventing  it  from  feeding  fuel  constantly. 
This  informs  the  user  about  failures  in  the 
electrical  system  controlling  the  fuel  feeder. 
In  case  of  alarm, 

stop  the  boiler  and 

repair the regulator as soon as possible.

  

It  is  also  possible  to  continue  operation  in 
emergency 

mode. 

Before 

continuing 

operation,  mane  sure  that  the  combustion 
chamber does not contain excessive unburnt 
fuel.  If  so,  remove  the  excess  fuel.  Ignition 
with excessive fuel may lead to  explosion of 
combustion  gasses!  Emergency  mode  is 
activated 

after 

entering 

the 

special 

password: 

4445. 

Before 

activating 

emergency  mode,  familiarize  yourself  with 
the  user  manual.  After  accepting  the 
password, the feeder control is taken over by 
the  emergency  system  and  the  boiler 
continues to operate.  

 

Note:  operating  in  emergency 
mode  is  allowed  only  under  user 
supervision  and  until  the  arrival  of 
the  service  team  to  remove  the 

failure.  If  user  supervision  is  not 
possible,  extinguish  the  boiler.  
When  operating  in  emergency 
mode, prevent the consequences of 
improper  feeder  work  (feeder 
working constantly or not at all). 

9.4

 

Boiler temp. sensor failure 

This  alarm 

occurs 

when 

the 

boiler 

temperature  sensor  is  damaged  or  when  its 
measurement  range  is  exceeded.  Check  the 
sensor and replace it if necessary.  

 

See  temperature  senor  check  in  pt. 
13.10. 

9.5

 

Feeder temp. sensor failure 

This  alarm  occurs  when  the  sensor  is 
damaged  or  when  its  measurement  range  is 
exceeded.  

 

See  temperature  senor  check  in  pt. 
13.10. 

9.6

 

Exhaust temperature sensor failure 

This  alarm  occurs  when  the  sensor  is 
damaged  or  when  its  measurement  range  is 
exceeded.  

 

See  temperature  senor  check  in  pt. 
13.10. 

9.7

 

Boiler ignition failed 

This  alarm  occurs  after  the  third  failed 
attempt  to  automatically  ignite  the  furnace 
The  causes  of  this  alarm  include:  faulty 
igniter or fan, damaged fuel feeding system, 
improper  parameter  settings,  low  fuel 
quality, lack of fuel in the container. 

 

Note:  Before  continuing  operation, 
make  sure  that  the  combustion 
chamber 

does 

not 

contain 

excessive  unburnt  fuel.  If  so, 
remove  the  excess  fuel.  Ignition 
with  excessive  fuel  may  lead  to 
explosion of combustion gasses!  

9.8

 

Exhaust temperature not met. 
Check fuel quality 

This  alarm  is  sounded  when  the  exhaust 
gases  are  not  heated  above  the  lack  of  fuel 
detection 

threshold 

in 

the 

exhaust 

temperature  increase  time.  The  alarm 
prevents filling the combustion chamber with 

Summary of Contents for ecoMAX860P2-T

Page 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Page 2: ...2...

Page 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Page 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Page 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Page 6: ......

Page 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Page 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Page 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Page 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Page 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Page 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Page 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Page 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Page 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Page 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Page 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Page 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Page 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Page 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Page 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Page 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Page 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Page 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Page 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Page 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Page 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Page 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Page 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Page 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Page 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Page 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Page 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Page 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Page 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Page 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Page 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Page 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Page 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Page 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Page 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Page 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Page 43: ......

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Reviews: