MC³ 24.96.EX O&M Manual
Page 12
08/14/01 4:34 PM/LDD
Switches (page 26).
GOOD
Good. This indicator is on when all of the following conditions have been met. If any
one of the conditions are not met this indicator will not activate.
1.
The setpoint method is not Manual Speed.
2.
The Feeder Block input is OFF (see Digital Inputs Setup on page 36).
3.
The Run Permission input is ON (see Digital Inputs Setup on page 36).
4.
The controller is in Gravimetric Mode (see Digital Inputs Setup on page 36).
5.
No Calibration procedures are running.
6.
The controller is not in its power up sequence.
7.
Feeder Run output is ON.
8.
The PID controller algorithm output is in its active domain.
9.
There are no General Alarms.
10.
The Feedrate has not exceed the Hi Feedrate Limit or Low Feedrate Limit.
LO
Low Feedrate - This indicator is on when a low feedrate condition exists. The type and
value of Low Limit Switch is determined by the operator. When this indicator is off the
feedrate is not below the value set in Limit Switches (page 26).
RMT
Remote - This indicator is on when the keypad has been locked through serial
communications. For more information on MC³ Serial Communications see [1]. The
remote device may be SuperBridge or another MC³. This indicator is off during normal
keypad operation.
AUTO
Auto - When this indicator is on, the controller is in the Automatic Setpoint Control
Mode. This is active when a Setpoint mode other than Manual Speed is active. If the
controller is in Manual Setpoint the indicator will be off. See Page 15 for a complete
explanation of the Setpoint modes
RPER
Run Permission - This indicator will be on when the Logical Input Run Permission is
ON. Run Permission clamps the speed demand output from the controller to Zero
when OFF. With this input ON the controller is able to control the process (see Digital
Inputs Setup on page 36).
GRAV
Gravimetric ON - This indicator follows the Logical Input Gravimetric ON. (see Digital
Inputs Setup on page 36).
ZTRK
Zero Tracking - This indicator will be on when Zero Tracking is turned on and the
procedure is currently running. See Zero Tracking Parameters on page 28 for more
information.
FBLK
Feeder Block - This indication follows the Logical Input ‘Feeder Block’. See Digital
Inputs Setup on page 36 for more information.
General Alarms
The general alarm button is used to indicate that a problem may exist. This button will
remain on until the conditions that caused the alarm have been removed and the alarm
acknowledged. To view the condition (or conditions) which has caused a General Alarm,
touch the alarm button. All alarms will be displayed with an indicator to the left of the text ( = ON
= OFF). You may still access this screen from the action menu.