MC³ 90.10.EX O&M Manual
- 27 -
Minimum Scale Values
This is the value representing the zero value used for scaling the inputs.
Panel Meter Units
0
Amps
1
Volts
2
Torque %
3
Temp ºF
4
Temp ºC
5
Incl º
Analog Input Cal
This procedure allows you to setup your analog inputs.
Touch the number of the analog input to calibrate to edit the analog input alarm values.
Adjust the input for a zero level. The live counts will vary accordingly. When zero is reached
touch the snap zero button. The live value will snap to the new value column.
Adjust the input for full-scale level. The live counts should follow the input. When the full level
has been reached touch the Snap full button. The live value will snap to the new Hi column.
If the values you selected are correct for your application, touch the accept button. The controller
will move the values from the New column to the Current column and start using the new values.